Adiabatic Equation Calculator — Short-Circuit Withstand

Minimum conductor size to survive a fault, S = √(I²t) ÷ k, to BS 7671 Regulation 543.1.3 — with k derived from the conductor material and its permitted temperature rise rather than looked up.

The adiabatic equation gives the smallest conductor that survives a fault without exceeding its permitted temperature: S = √(I²t) ÷ k, where S is the cross-section in mm², I the fault current in amperes, t the disconnection time of the protective device in seconds, and k a constant for the conductor material and the temperature rise it is allowed. For copper inside a 70 °C thermoplastic cable, k = 115; for the same copper run separately as a protective conductor it is 143, because it starts at 30 °C instead of 70 °C. A 1 500 A fault cleared in 0.1 s therefore needs √(1500² × 0.1) ÷ 115 = 4.13 mm², so 6 mm². The equation assumes no heat leaves the conductor and is valid only up to about 5 seconds.

Formula
S = √(I²t) ÷ k
Regulation
BS 7671 543.1.3
k formula
√[Qc(β + 20) ÷ ρ₂₀ × ln((β + θf) ÷ (β + θi))]
Copper in a 70 °C cable
k = 115
Copper cpc run separately
k = 143
Steel armour, 90 °C thermosetting
k = 52
Validity limit
t ≤ 5 s

Inputs

This sets the starting temperature, and it changes the answer by about 25%. A conductor carrying load is already hot when the fault arrives; one run separately sits at ambient.

Conductor material

Steel is here because a cable’s armour is very often the circuit protective conductor.

Fault energy from

For a current-limiting device, the published let-through energy is the correct input — current × time overstates it badly.

A

The prospective fault current at the point of the fault.

s

From the device’s time/current characteristic at this fault current. Valid to 5 s.

In mm². Optional — leave it as it is to see the minimum on its own, or enter your chosen size for a pass/fail.

Results

Minimum size (mm²)4.131S = √(I²t) ÷ k
Smallest standard size (mm²)
6
k factor
114.8
Let-through energy (A²s)
2.250e+5
Your conductor withstands
211 ms
Margin over minimum (mm²)
1.869

k = 114.8 for copper going from 70 °C to 160 °C — a protective conductor inside a cable or bunched with one, 70 °C thermoplastic (PVC), ≤ 300 mm². Derived from k = √[Qc(β + 20) ÷ ρ₂₀ × ln((β + θf) ÷ (β + θi))], not looked up.

4.13 mm² is the bare minimum; 6 mm² is the smallest standard size that meets it. Never round down here — the calculation already assumes every joule stays in the conductor, and the margin between 4.13 and the next size down is not spare capacity, it is the difference between surviving the fault and not.

6 mm² passes: it is above the 4.13 mm² minimum, with 1.9 mm² in hand. At this fault current it withstands 0.211 s, against the 0.1 s the device needs.

Let-through energy 2.25e+5 A²s. That single number is all the conductor cares about — the same energy delivered as a huge current briefly or a smaller one for longer produces the same temperature rise, which is why S depends on √(I²t) and not on I and t separately.

Passing the adiabatic check does not make a protective conductor compliant on its own — it also has to satisfy the disconnection time for the earth fault loop impedance, and be at least the size Table 54.7 requires where that route is used.

Worked examples

1.5 mm² cpc in twin and earth

The classic domestic case. A 2.5 mm² ring with a 1.5 mm² cpc, a 1 500 A fault cleared by a 32 A Type B MCB in 0.1 s.

k = 114.8, minimum 4.13 mm² — 1.5 mm² fails on current-and-time. See the next preset.

The same fault, using the device let-through

The same circuit, but taking the MCB’s published I²t instead of assuming the full prospective current flows for the whole disconnection time. This is what a current-limiting device actually does.

Minimum 1.31 mm² — 1.5 mm² passes. Same circuit, a third of the conductor.

SWA armour as the cpc

A 90 °C thermosetting SWA sub-main where the steel armour is the protective conductor. Steel has about a third of copper’s k, so the armour has to be checked rather than assumed.

k = 51.7, minimum 26.0 mm² of armour — 35 mm² passes with 9 mm² in hand.

A separate cpc — the same copper, more headroom

The identical conductor run on its own rather than inside the cable. It starts at 30 °C instead of 70 °C, so k rises from 115 to 143 and the minimum size falls by a fifth.

k = 142.7, minimum 3.32 mm² — 4 mm² passes where it was marginal bunched.

A long disconnection time — outside the method

A 5.5 s clearance, past the point where treating the fault as adiabatic is safe. The calculator gives the arithmetic and tells you not to rely on it.

Minimum 10.2 mm², so 10 mm² fails — and 5.5 s is past the equation’s 5 s validity limit anyway.

Reviewed by Salamot Hok, electrician with 10+ years · Last reviewed 25 August 2026

Engineering guidance, not a code sign-off. Verify against the governing standard before relying on this result for safety-critical or code-compliance work.

What the adiabatic check actually asks

When to use this: sizing a circuit protective conductor that is smaller than the line conductors, deciding whether an SWA cable’s armour is adequate as the cpc, checking a reduced cpc in twin and earth, or justifying a conductor size on a design that somebody will inspect.

Every other cable calculation on this site is about normal service — will the cable carry the load without overheating, will the load get the voltage it needs. This one is about the few hundred milliseconds when everything has already gone wrong.

A fault puts thousands of amps through a conductor sized for tens. The protective device will clear it; that is not in question. The question is whether the conductor is still a conductor afterwards, or whether the copper has spent a fifth of a second at 400 °C and the insulation around it has quietly stopped being insulation.

S = √(I²t) ÷ k

S is the minimum cross-section in mm², I the fault current in amperes, t the disconnection time in seconds, and k a constant that carries both the conductor material and the temperature rise it is allowed. It is Regulation 543.1.3 in BS 7671.

What “adiabatic” buys, and what it costs

An adiabatic process is one where no heat enters or leaves the system. Applied here it means assuming that every joule of fault energy goes into raising the temperature of the conductor itself, and none of it escapes into the insulation, the armour, the terminations or the surrounding air.

That is not true. It is, however, conservative, and it is very nearly true for the short durations a fault lasts — which is what makes a one-line equation usable in place of a thermal model. The price is a hard validity limit: about 5 seconds. Past that, enough heat has genuinely left the conductor that the assumption stops being a safe simplification and starts being wrong in a way that depends on the installation, which the equation has no way to represent. The calculator says so when you cross it.

Where k comes from — and why this page derives it

Most calculators offer k as a dropdown of published values. This one computes it:

k = √[ Qc(β + 20) ÷ ρ₂₀ × ln((β + θf) ÷ (β + θi)) ]

Qc is the conductor’s volumetric heat capacity, β the reciprocal of its temperature coefficient of resistivity at 0 °C, and ρ₂₀ its resistivity at 20 °C. θi is the temperature the conductor is at when the fault starts; θf is the highest it may reach.

Read the equation in two halves and the whole subject becomes clear. The first bracket is a property of the metal and never changes — it works out at 226 for copper, 148 for aluminium and 78 for steel. The logarithm is the entire design decision: how hot the conductor already was, and how hot it is allowed to get.

Every published k table is those two temperatures and nothing else. That is why deriving k is both legitimate and more useful than looking it up: a construction the tables do not list still gets a defensible number. The reference page prints the derived value beside the published one for every row of the standard, so you can check the claim rather than take it.

The mistake that changes the answer by a quarter

There are three k tables, and the difference between them is only θi — the temperature the conductor starts at.

  • A line conductor is carrying its load when the fault arrives, so it starts at the cable’s rated operating temperature: 70 °C for thermoplastic, 90 °C for thermosetting.
  • A protective conductor inside a cable, or bunched with one, carries no load current itself but is heated by the conductors around it, so it starts at the same temperature they do.
  • A protective conductor run separately carries nothing and is next to nothing, so it sits at ambient — taken as 30 °C.

Same copper, same insulation, same fault. Inside the cable, k = 115. Run on its own, k = 143. That is a 20% difference in the conductor you need, in both directions: read the separate-conductor row for a cpc that is actually inside the cable and you will undersize it.

The headroom is real but conditional. A cpc is only “separate” while it genuinely is — pull it through the same conduit as the loaded conductors and it is heated by them, and the bunched figure applies again.

Steel armour as the cpc

On an SWA run the armour is very often the circuit protective conductor, and this is the calculation that decides whether it may be. Steel’s k is roughly a third of copper’s — 52 against 143 for a 90 °C thermosetting cable — so the armour needs about three times the cross-sectional area to survive the same fault.

On larger cables it comfortably has that. On smaller ones it frequently does not, which is the reason a separate cpc gets pulled in alongside an SWA cable that appears to have a perfectly good earth path already. Take the armour’s cross-sectional area from the manufacturer’s data for the specific cable — it is published, and it is not proportional to the conductor size in any way you can guess.

Disconnection time, or let-through energy?

This is where most adiabatic calculations go wrong, and always in the expensive direction.

The obvious method is to read the prospective fault current at the point of the fault, look up the disconnection time on the device’s time/current characteristic, and multiply. For a slow device that is right. For a current-limiting device it is badly wrong: the device interrupts the fault before the current reaches its first peak, so the conductor never experiences the full prospective current, and never for the full time you read off the curve.

Manufacturers publish what actually gets through as a let-through energy, in A²s, per device and per prospective fault level. Use it whenever it exists. The two presets on this page show the same 1.5 mm² cpc failing on current-and-time and passing on let-through energy — a three-fold difference in required conductor, for one circuit, from choosing the right input.

If the conductor fails

Four options, roughly in order of cost:

  1. A faster or current-limiting device. Usually the cheapest fix, and it attacks the actual problem — the energy reaching the conductor — rather than compensating for it.
  2. Run a separate cpc rather than relying on the armour or a reduced conductor inside the cable. Worth a quarter on its own.
  3. A larger conductor. Always works, always costs.
  4. Reduce the prospective fault current. Effective, and almost always outside your control.

What passing this does not prove

Surviving the fault is one requirement out of several, and it is easy to treat it as the whole job because it produces a satisfying number. A protective conductor also has to give an earth fault loop impedance low enough that the device disconnects within the required time — a separate calculation with a separate failure mode — and where the Table 54.7 route is used it must meet that table’s minimum size regardless of what the adiabatic equation says.

The adiabatic equation is the alternative to Table 54.7 for sizing. It is not an alternative to the disconnection time requirement, and nothing on this page evaluates that.

How to use this calculator

  1. Say what the conductor is

    A protective conductor inside a cable, one run separately, or a line conductor. This sets the temperature the conductor starts at, and it moves the answer by about 25% — a separately run cpc sits at ambient while one bundled with loaded conductors is already at the cable’s operating temperature.

  2. Pick the construction and material

    The insulation type sets the highest temperature the conductor may reach. Steel is offered because a cable’s armour is very often the cpc, and steel has roughly a third of copper’s k.

  3. Enter the fault energy

    Either the prospective fault current and the disconnection time from the device’s time/current curve, or — for a current-limiting device — the published let-through I²t in A²s. The second is more accurate and usually gives a much smaller conductor.

  4. Read the minimum, and round up

    The result is the bare minimum. Take the next standard size above it, never the one below: the calculation already assumes every joule stays in the conductor, so there is no hidden margin to spend.

  5. Enter your chosen size for a verdict

    Put the size you intend to install in the last field and the calculator says pass or fail, and how long that conductor actually survives this fault.

  6. Remember what this does not prove

    Surviving the fault is one requirement. The protective conductor must also give a low enough earth fault loop impedance to disconnect in the required time, and meet the Table 54.7 minimum where that route is used.

Frequently asked questions

What is the adiabatic equation?

S = √(I²t) ÷ k, from BS 7671 Regulation 543.1.3. It gives the smallest conductor cross-section in mm² that can carry a fault current I for a time t without its temperature exceeding the limit its insulation and terminations can survive. "Adiabatic" means the calculation assumes none of the heat escapes the conductor during the fault — everything goes into raising its temperature. That is conservative and close to true for the fraction of a second a fault lasts, which is also why the equation is only valid up to about 5 seconds.

What is the k factor and where does it come from?

k combines the conductor material’s properties with the temperature rise it is permitted. It is calculated as k = √[Qc(β + 20) ÷ ρ₂₀ × ln((β + θf) ÷ (β + θi))], where Qc is volumetric heat capacity, β the reciprocal of the temperature coefficient of resistivity at 0 °C, ρ₂₀ the resistivity at 20 °C, θi the temperature when the fault starts and θf the highest permitted. The first part is fixed by the metal — 226 for copper, 148 for aluminium, 78 for steel. Everything else in a published k table is a choice of those two temperatures. This calculator derives k rather than looking it up, which is why it can handle constructions the tables do not list.

Why is k different for a cpc inside a cable and one run separately?

Only the starting temperature differs, and it changes the answer a lot. A protective conductor inside a cable, or bunched with loaded ones, is heated by its neighbours and sits at the cable’s operating temperature — 70 °C for thermoplastic. One run separately carries no load current and sits at ambient, taken as 30 °C. That extra 40 °C of headroom takes copper from k = 115 to k = 143, which is about 20% less conductor for the same fault. Reading the wrong table is one of the commonest errors in this calculation.

What is k for copper?

It depends on the temperatures, not just the metal. Copper inside a 70 °C thermoplastic cable is 115. The same copper run separately with a thermoplastic covering is 143, because it starts at 30 °C. Copper inside 90 °C thermosetting insulation is also 143, but for a different reason — it starts hotter and is allowed to reach 250 °C. A bare copper conductor that is visible and in a restricted area reaches 228, because it is permitted to go to 500 °C.

Can steel wire armour be used as the cpc?

Often yes, and this is the calculation that decides. Steel’s k is roughly a third of copper’s — 52 against 143 for a 90 °C thermosetting cable — so the armour needs about three times the cross-sectional area to survive the same fault. On larger SWA the armour usually has that area comfortably. On smaller sizes it frequently does not, which is why a separate cpc gets pulled in alongside. Check the armour area from the manufacturer’s data rather than assuming it.

Should I use disconnection time or the device’s let-through energy?

Use the let-through I²t whenever the device publishes it, especially for anything current-limiting. A current-limiting MCB or fuse interrupts the fault before it reaches its first peak, so the conductor never experiences the full prospective current for the full time read off a time/current curve. Multiplying I² by t in that case can overstate the energy several times over and demand a conductor two or three sizes larger than necessary. Manufacturers publish let-through energy per device and per prospective fault level.

Why is the adiabatic equation limited to 5 seconds?

Because the assumption it rests on stops holding. Over a few hundred milliseconds essentially all the fault energy stays in the conductor, so treating the heating as adiabatic is both simple and safe. Over several seconds a significant amount escapes into the insulation, the armour, the surrounding air and the terminations — and the amount depends on the installation in a way the equation has no way to represent. Past 5 seconds you need a full thermal calculation, or a device that clears faster.

My conductor fails the adiabatic check. What are my options?

Four, roughly in order of cost. Use a faster or current-limiting protective device, which cuts the let-through energy and is often the cheapest fix. Reduce the prospective fault current, though that is usually outside your control. Increase the conductor size. Or, if the protective conductor is what failed, run a separate one rather than relying on the armour or a reduced cpc inside the cable — that alone changes k by a quarter.

Does passing the adiabatic check make my cpc compliant?

No. It proves the conductor survives the fault, which is one requirement of several. The protective conductor also has to give an earth fault loop impedance low enough that the device disconnects within the required time, and where the Table 54.7 route is used it must meet that table’s minimum size regardless of what the adiabatic calculation says. The adiabatic equation is the alternative to Table 54.7, not a substitute for the disconnection time requirement.

Why does the answer use √(I²t) rather than I and t separately?

Because the conductor only responds to energy, and I²t is the energy the fault delivers to it. A very large current for a very short time and a smaller current for longer produce the same temperature rise if I²t is the same, and the conductor cannot tell them apart. That is why protective device manufacturers publish let-through energy as a single I²t figure, and why the equation takes the square root of it.

Does this apply to line conductors too?

Yes, and it is required, but it rarely decides anything. A line conductor has already been sized for its load current and for voltage drop, and a conductor big enough for those is nearly always big enough to survive a fault. The check bites on protective conductors, which are routinely sized down — halved under Table 54.7, or taken as the armour of a cable — and therefore have far less material to absorb the same energy.

Sources and further reading

How this calculator is checked

Salamot Hok, Technical reviewer

Technical reviewer

Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region

He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.

  • The maths lives in a pure function with its own test suite, asserted against worked examples from published references and standards. A calculator does not ship until those tests pass.
  • 4 sources cited by name and linked, so any figure on the page can be traced back to the document it came from.
  • Last reviewed . Review dates are advanced only when the page is actually re-read, never to look fresh.
  • Unusable input returns no answer. Where the inputs do not describe a real design, the calculator says so and withholds the number rather than printing a plausible-looking wrong one.

Related calculators