Typical branch circuit — 3 × 12 AWG in 1/2" EMT
Hot, neutral and ground for a 20 A circuit. The most common run there is.
13.1% of a 40% limit — plenty of room
How many conductors fit in a conduit, and what size you need. EMT, IMC, RMC and PVC with the real Chapter 9 table areas — including the 31% rule that catches people out.
THHN is the usual choice. THW is much fatter and can cost you a conduit size.
Use a third group for a smaller equipment grounding conductor.
A conduit 24 inches or shorter between enclosures may be filled to 60%.
Conductors: 3 × 12 AWG (0.0399 in²) = 0.0399 in² total.
13.1% fill against a 40% limit — compliant, with 0.0817 in² spare.
Room for roughly 6 more conductors of the largest size before the limit — though adding current-carrying conductors also triggers ampacity derating under 310.15.
Hot, neutral and ground for a 20 A circuit. The most common run there is.
13.1% of a 40% limit — plenty of room
Two conductors are limited to 31%, not 40%. Most people assume 40% applies to everything.
Limit drops to 31% simply because there are two rather than three
A shared raceway. Watch the derating note once you pass three current-carrying conductors.
Fits 3/4" comfortably, but ampacity derating now applies
A 175 A feeder. Large conductors fill a conduit far faster than people expect.
26.5% in 2" EMT
When to use this: deciding what size conduit to buy before a run, checking whether you can add another circuit to an existing raceway, or verifying an inspector's objection.
Three NEC Chapter 9 tables do all the work:
Add up the conductor areas, divide by the conduit area, and compare against the Table 1 percentage. That is the entire calculation.
| Number of conductors | Maximum fill |
|---|---|
| 1 | 53% |
| 2 | 31% |
| 3 or more | 40% |
| Nipple ≤ 24" | 60% |
Two conductors are limited to 31% — less than three or more. That looks like a misprint and it is not. Two round conductors side by side in a round conduit leave the most awkward unusable space, and they are the hardest case to pull because neither can shuffle past the other. Three or more pack better and move more freely.
Most people assume 40% applies universally. On a two-wire run — a switch leg, a 240 V circuit with no neutral — that assumption puts you 29% over the real limit.
The conductors physically fit at 70% or 80%. The limit is not about space, it is about two practical problems:
At the 40% limit. This is the table most people actually want.
| AWG | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" |
|---|---|---|---|---|---|---|
| 14 | 12 | 21 | 35 | 61 | 83 | 138 |
| 12 | 9 | 16 | 25 | 44 | 61 | 100 |
| 10 | 5 | 10 | 16 | 28 | 38 | 63 |
| 8 | 3 | 5 | 9 | 16 | 22 | 36 |
| 6 | 2 | 4 | 6 | 11 | 16 | 26 |
| 4 | 1 | 2 | 4 | 7 | 9 | 16 |
| 2 | 1 | 1 | 2 | 5 | 7 | 11 |
| 1/0 | — | 1 | 1 | 3 | 4 | 7 |
| 2/0 | — | — | 1 | 2 | 3 | 6 |
| 4/0 | — | — | 1 | 1 | 2 | 4 |
Note how fast large conductors eat a conduit. One 4/0 is 0.3237 in² — more than the entire internal area of 1/2 inch EMT.
The conductor area in Table 5 is the insulated area, so insulation thickness matters as much as the copper:
| AWG | THHN | XHHW | THW |
|---|---|---|---|
| 14 | 0.0097 | 0.0139 | 0.0209 |
| 12 | 0.0133 | 0.0181 | 0.0260 |
| 10 | 0.0211 | 0.0243 | 0.0333 |
| 8 | 0.0366 | 0.0437 | 0.0556 |
| 6 | 0.0507 | 0.0590 | 0.0726 |
THW 12 AWG is 0.0260 in² against THHN's 0.0133 — almost double. Nine THHN 12 AWG conductors fit in 1/2 inch EMT; only four THW do. Specifying the wrong insulation on a materials list can cost you a conduit size across an entire job.
Internal area at the same trade size, square inches:
| Trade size | IMC | RMC | EMT | PVC 40 | PVC 80 |
|---|---|---|---|---|---|
| 1/2" | 0.342 | 0.314 | 0.304 | 0.285 | 0.217 |
| 3/4" | 0.586 | 0.549 | 0.533 | 0.508 | 0.409 |
| 1" | 0.959 | 0.887 | 0.864 | 0.832 | 0.688 |
| 1-1/4" | 1.647 | 1.526 | 1.496 | 1.453 | 1.237 |
| 2" | 3.630 | 3.408 | 3.356 | 3.291 | 2.874 |
IMC is roughly 12% roomier than EMT at the same trade size; PVC Schedule 80 is about 28% tighter. "1 inch conduit" is not one thing.
This is the most common misunderstanding, and both must be satisfied independently.
| Conduit fill | Ampacity derating | |
|---|---|---|
| Where | Chapter 9, Table 1 | 310.15(C)(1) |
| Limits | Physical space | Current rating |
| Counts | Every conductor, including grounds | Current-carrying conductors only |
| Triggers at | Always | More than 3 current-carrying |
Derating factors once you pass three:
| Current-carrying conductors | Ampacity |
|---|---|
| 4–6 | 80% |
| 7–9 | 70% |
| 10–20 | 50% |
So a 3/4 inch EMT holding nine 12 AWG conductors is comfortably within fill — but those conductors are derated to 70%, and 12 AWG THHN at 30 A becomes 21 A, which no longer supports a 20 A breaker with the required margin. Legal on fill, non-compliant on ampacity.
Two 20 A circuits plus a shared ground, in EMT:
4 × 12 AWG THHN (hots and neutrals) = 4 × 0.0133 = 0.0532 in²1 × 14 AWG THHN (ground) = 0.0097 in²Total = 0.0629 in², 5 conductors → 40% limit
1/2 inch EMT is 0.304 in², so 40% is 0.1216 in². The bundle at 0.0629 in² is 20.7% fill — comfortably compliant.
But four of those five are current-carrying, so derating applies at 80%. The 12 AWG THHN drops from 30 A to 24 A, which still supports a 20 A breaker. Both limits satisfied.
EMT, IMC, RMC and PVC all have different internal areas at the same trade size. PVC Schedule 80 has notably less room than Schedule 40.
THHN is the default. THW has much thicker insulation — nearly double the area at 12 AWG — which can push you up a conduit size on its own.
Up to three groups, so you can mix sizes. A typical circuit is two or three current-carrying conductors plus a smaller ground.
The permitted percentage depends on how many conductors there are: 53% for one, 31% for two, 40% for three or more.
It depends on the number of conductors, from Chapter 9 Table 1: one conductor may fill 53%, two conductors 31%, and three or more 40%. Conduit nipples of 24 inches or less between enclosures are permitted 60%.
Geometry. Two round conductors side by side in a round conduit leave the most awkward unusable space and are the hardest case to pull. Three or more pack more efficiently and can shuffle past each other during the pull. It looks like an error in the table but it is deliberate.
Nine THHN 12 AWG conductors in 1/2 inch EMT. Each is 0.0133 in², the conduit is 0.304 in², and 40% of that is 0.1216 in² — enough for nine. This matches NEC Annex C, which tabulates the answer directly.
The limit is not about whether they fit. It is about being able to pull them without stripping insulation on the conduit wall or on each other, and about letting the conductors shed heat. Conductors physically fit well past 40%; they just cannot be installed or cooled safely at that density.
Yes, for fill purposes. Every conductor in the raceway counts toward the cross-sectional area, including grounds and neutrals. For ampacity derating, though, the rules differ — an equipment grounding conductor is not a current-carrying conductor, and a neutral only counts in certain configurations.
They are separate limits and you must satisfy both. Fill is a physical space limit from Chapter 9. Derating is an ampacity reduction under 310.15(C)(1) once more than three current-carrying conductors share a raceway — 80% for 4 to 6 conductors, 70% for 7 to 9. A conduit can be legally filled and still have conductors that are no longer rated for their breaker.
Yes. At the same trade size, IMC has the largest internal area, then RMC, then EMT, then PVC Schedule 40, with PVC Schedule 80 smallest because of its thicker walls. The difference is enough to matter — 1 inch IMC has 0.959 in² against 0.688 in² for 1 inch PVC 80.
A length of conduit 24 inches or shorter connecting two enclosures. Because there is no meaningful pull distance and no length over which to trap heat, Chapter 9 Note 4 permits 60% fill instead of 40%. Derating is also waived for nipples.
Last reviewed .
Diameter, cross-section, resistance and current rating for any AWG size — with separate free-air and in-conduit ampacity, because they differ by a factor of two.
kVASize a house service the way an electrician does: NEC Article 220 standard calculation, with the demand factors that stop a 40 kW house needing a 400 A service.
ΔVVoltage drop for DC, single-phase and three-phase runs in copper or aluminium, sized in mm² or AWG, checked against IEC and NEC limits.
3ØkW, kVA and kVAr from line voltage and current, with star and delta phase values and what power factor correction would save you.