Wire Size Calculator — NEC Ampacity and Voltage Drop

What size wire you need, from the load, the run length and the conditions — sized against both NEC ampacity and voltage drop, with the terminal temperature rule that stops 90 °C wire giving 90 °C ampacity.

Inputs

A

In amperes. For a watts figure, divide by the voltage first.

V

Line-to-line for three phase. Higher voltage tolerates far longer runs.

System
Continuous load

A load expected to run for 3 hours or more is sized at 125% per 210.19(A)(1).

Distance from the panel to the load, not there and back.

Length in
Conductor material

The wire itself. This sets what you derate FROM, not what you may use.

Terminal rating

Per 110.14(C). Modern breakers and panels are usually listed 75 °C — check the label.

In °C. Tables assume 30 °C. An attic in summer is 50 °C or more.

In the same raceway or cable. Grounds never count; see the notes on neutrals.

%

3% for a branch circuit, 5% for feeder plus branch combined — both recommendations, not rules.

Results

Wire size required12 AWGlarger of ampacity and voltage-drop size
Ampacity alone would need
12 AWG
Voltage drop alone would need
14 AWG
Design current
20 A
Usable ampacity
20 A
Overcurrent device
20 A
Voltage drop
1.61 %
Volts lost in the run
3.863 V

12 AWG is set by ampacity. Ampacity alone would allow 12 AWG; voltage drop alone would need 14 AWG.

240.4(D) caps this size at 20 A regardless of the table. This is why 12 AWG THHN, which shows 30 A in the 90 °C column, still belongs on a 20 A breaker.

Voltage drop at 12 AWG: 3.86 V, 1.61% — arriving at 236.1 V. The 3% branch-circuit figure is a recommendation in an Informational Note, not an enforceable rule.

Diagram

Which constraint sets the wire sizeAmpacity requires 12 AWG, voltage drop requires 14 AWG, so the conductor is 12 AWG with 1.61% drop.What sets the sizeAmpacity needs12 AWGVoltage drop needs14 AWGUse 12 AWGDrop at that size1.61%limit 3%

Worked examples

20 A kitchen circuit, 50 ft

The everyday case. Short run, so ampacity decides.

12 AWG — capped at 20 A by 240.4(D), not by the 30 A table entry

The same 20 A load, 200 ft away

A detached garage or workshop. Watch the answer jump two sizes for a load that has not changed.

8 AWG — voltage drop governs; ampacity would still permit 12 AWG

Attic run, 50 °C, six conductors

Where derating bites. Same load, much worse conditions.

6 AWG — ambient 0.82 × fill 0.80 = 0.656 on the 90 °C column. In benign conditions the same load takes 8 AWG

100 A subpanel feeder in aluminium

The usual choice for a long feeder. Compare against copper.

1 AWG aluminium — exactly two sizes above the 3 AWG copper the same feeder would take

30 A continuous — an EV charger

Continuous loads are sized at 125%. This is why a 32 A charger needs a 40 A circuit.

40 A design current — 8 AWG on a 40 A breaker

Wire sizing has two answers, and you take the larger

When to use this: running a new circuit, feeding a detached building, adding an EV charger, or checking whether existing wire is adequate for a bigger load.

Two independent constraints decide the size, and they behave completely differently:

  • Ampacity — can the conductor carry the current without overheating? Set by NEC Table 310.16, then reduced for heat, then capped by the terminals. Does not depend on distance at all.
  • Voltage drop — will enough voltage still be there at the far end? Grows linearly with distance and never stops growing.

On a short run ampacity decides and voltage drop is irrelevant. Past roughly 100 ft they swap over, and from then on distance is the only thing that matters. A calculator that checks only ampacity will happily tell you 12 AWG is fine for a 20 A load 300 ft away. It is legal. It is also useless — the load will see about 19% less voltage than it should.

The rule that catches everyone: 110.14(C)

You buy THHN. Its jacket says 90 °C. Table 310.16 says 12 AWG copper carries 30 A in the 90 °C column. So a 30 A breaker, surely?

No. Two separate rules stop you, and both are easy to miss.

  1. NEC 110.14(C) — the ampacity of a circuit is limited by the lowest temperature rating of any connected part, and that is the terminals on the breaker and the device. Terminals are listed for 60 °C or 75 °C. Essentially nothing in a panel is listed for 90 °C. Landing 90 °C wire on a 75 °C terminal makes it a 75 °C installation.
  2. NEC 240.4(D) — an absolute cap on the overcurrent device for small conductors, regardless of any table: 15 A for 14 AWG copper, 20 A for 12 AWG, 30 A for 10 AWG. No conditions, no exceptions worth relying on.

So 12 AWG THHN is a 30 A wire on paper, a 25 A wire after the terminal rule, and a 20 A wire after 240.4(D). The last number is the one you use.

Then why buy 90 °C wire?

Because derating starts from the 90 °C column. That is the one place the higher rating earns its money. Six conductors in a 50 °C attic get multiplied by 0.82 for ambient and 0.80 for conductor count — starting that multiplication from a bigger number leaves more at the end.

Worked through for 6 AWG copper: from the 90 °C column, 75 × 0.82 × 0.80 = 49.2 A. From the 75 °C column it would be 65 × 0.82 × 0.80 = 42.6 A. Same wire, same conditions, one full conductor size of difference — purely from which column you were entitled to start in.

The order matters and it is worth stating plainly: derate from the insulation column, then cap at the terminal column. Doing it the other way round is a common shortcut and it oversizes every derated run.

How much distance changes the answer

A 20 A load on a 240 V single-phase circuit, copper, 3% drop limit. The load never changes. Only the run does.

One-way distanceAmpacity needsVoltage drop needsAnswerDrop at that size
25 ft12 AWG14 AWG12 AWG0.80%
50 ft12 AWG14 AWG12 AWG1.61%
100 ft12 AWG10 AWG10 AWG2.03%
150 ft12 AWG8 AWG8 AWG1.91%
200 ft12 AWG8 AWG8 AWG2.55%
300 ft12 AWG6 AWG6 AWG2.40%
400 ft12 AWG4 AWG4 AWG2.01%

The ampacity column never moves. The drop column climbs relentlessly. At 400 ft the same 20 A load wants 4 AWG — a conductor sized for a load four times larger, bought entirely to fight resistance.

Voltage is the cheapest lever here, because drop as a percentage scales with 1/V. That same 20 A at 400 ft needs 2 AWG at 120 V and 4 AWG at 240 V. Running a 240 V circuit and stepping down at the far end is often cheaper than the copper you would otherwise buy.

Common circuits, sized

Copper, 75 °C terminals, 90 °C insulation, 30 °C ambient, three current-carrying conductors, non-continuous. The distance columns show where drop takes over.

CircuitTypical useAmpacity onlyAt 50 ftAt 100 ftAt 200 ft
15 ALighting, general receptacles14 AWG14 AWG12 AWG8 AWG
20 AKitchen, bathroom, laundry receptacles12 AWG12 AWG10 AWG8 AWG
30 ADryer, water heater, small subpanel10 AWG10 AWG8 AWG6 AWG
40 AElectric range, EV charger8 AWG8 AWG8 AWG4 AWG
50 ARange, welder, larger EV charger8 AWG8 AWG6 AWG4 AWG
60 ASubpanel, large HVAC6 AWG6 AWG6 AWG3 AWG
100 ASubpanel, small service3 AWG3 AWG3 AWG1 AWG
150 AService entrance1/0 AWG1/0 AWG1/0 AWG1/0 AWG
200 AStandard residential service3/0 AWG3/0 AWG3/0 AWG3/0 AWG

These are 240 V figures. At 120 V, halve the distance for the same drop — a 20 A 120 V circuit is already at 2.5% on 8 AWG by 100 ft.

NEC Table 310.16 — allowable ampacities

Not more than three current-carrying conductors in a raceway or cable, 30 °C ambient. These are the values before any derating and before the terminal limit.

SizeCopperAluminium
60 °C75 °C90 °C60 °C75 °C90 °C
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055304045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

Aluminium has no 14 AWG entry — the table starts at 12 AWG, and 14 AWG aluminium is not a branch-circuit conductor you can buy. Across the range, aluminium runs about two sizes behind copper for the same ampacity.

Derating factors

Ambient temperature — Table 310.15(B)(1)

The table is built for 30 °C. Anything hotter costs you ampacity, and the colder-rated the insulation, the harder it is punished.

Ambient60 °C column75 °C column90 °C column
25 °C1.081.051.04
30 °C1.001.001.00
35 °C0.910.940.96
40 °C0.820.880.91
45 °C0.710.820.87
50 °C0.580.750.82
55 °C0.410.670.76

A dash in the published table means the conductor may not be used at that ambient at all — shown here as "not permitted" rather than quietly treated as no correction, which is the dangerous reading. Note 60 °C wire is finished at 55 °C ambient while 90 °C wire keeps going to 85 °C.

Conductor count — Table 310.15(C)(1)

More than three current-carrying conductors sharing a raceway and they cook each other.

Current-carrying conductorsAdjustment
3100%
480%
680%
770%
1050%
2050%
2145%
4135%

What counts is the subtle part. Ungrounded conductors always count. Equipment grounding conductors never do. The neutral of an ordinary 120/240 V single-phase circuit does not count, because it only carries the unbalance between the two hots. But the neutral of a three-phase four-wire wye circuit feeding nonlinear loads — LED drivers, computer supplies, VFDs — does count under 310.15(E)(3), because triplen harmonics add in the neutral instead of cancelling. That neutral can carry more current than any phase.

Voltage drop: not a rule, still the thing that bites

The 3% branch-circuit and 5% combined figures live in Informational Notes to 210.19(A) and 215.2(A). Informational Notes are explicitly not enforceable requirements. No inspector will fail you for voltage drop on a dwelling branch circuit.

They are still worth designing to, because the failures are real and diffuse:

  • Motors draw more current at lower voltage to deliver the same power, so they run hotter and their service life falls. A 10% low-voltage condition is roughly a halving of insulation life.
  • Resistive heating falls off with the square of voltage. 10% low is 19% less heat, which reads to the user as an underperforming appliance.
  • Starting current makes drop far worse momentarily — which is why lights dim when the compressor kicks in.
  • It gets worse over time as connections oxidise and loosen, so a design sitting exactly at the limit will not stay there.

This calculator figures drop from conductor resistivity at 75 °C rather than the K-constant shortcut, so it agrees with our voltage drop calculator exactly. That works out to K ≈ 12.6 for copper against the textbook 12.9 — about 2%, and in the conservative direction against most published tables.

Things that change the answer and are easy to forget

  • Continuous loads. Anything running three hours or more is sized at 125% per 210.19(A)(1). EV charging, electric heat and commercial lighting all qualify. This is why a 32 A charger needs a 40 A circuit.
  • Motors use table values, not nameplates. NEC 430.6(A) says to size conductors from Table 430.250, whatever the plate says. Then 430.22 applies 125%.
  • Aluminium terminations. The metal is fine; the terminations are what failed in 1960s branch wiring. Use listed AL or CO/ALR devices, brush the conductor and use antioxidant compound.
  • Stranded and solid are the same ampacity. Table 310.16 makes no distinction. Stranded is slightly fatter overall, which matters for conduit fill, not for current.
  • Buried and free-air runs use different tables. Table 310.16 is for raceways and cables. Direct burial and free air have their own tables with higher values.
  • Parallel conductors are allowed at 1/0 and above under 310.10(G), and all the parallel conductors must be the same length, material and size.

Once you have a size, check it fits: our conduit fill calculator works to NEC Chapter 9, and the load calculator works out the service size those feeders have to come from.

How to use this calculator

  1. Enter the load and the voltage

    In amperes. If you have a wattage, divide by the voltage first. For motors use the table FLC from NEC 430.250, not the nameplate current.

  2. Say whether the load is continuous

    Anything expected to run for three hours or more — EV charging, electric heating, most commercial lighting. The conductor is then sized to 125% of the load.

  3. Enter the one-way run length

    From the panel to the load, measured along the actual cable path rather than in a straight line. The calculator handles the return conductor itself.

  4. Set the conditions

    Ambient temperature and the number of current-carrying conductors sharing the raceway. Both derate the conductor, and both are routinely left out of hand calculations.

  5. Check the terminal rating

    Look at the label on your breaker and panel. Most modern equipment is listed for 75 °C; older or smaller equipment may be 60 °C only. This caps your ampacity regardless of the wire you buy.

  6. Read which constraint governed

    The result shows the size ampacity needs and the size voltage drop needs. On a short run they differ and ampacity wins; past roughly 100 ft the drop takes over.

Frequently asked questions

What size wire do I need for 20 amps?

12 AWG copper for a typical run. 14 AWG is limited to 15 A by NEC 240.4(D), so it cannot serve a 20 A circuit no matter what its insulation is rated for. Distance changes the answer fast at 120 V: keeping drop under 3% needs 10 AWG by 50 ft and 8 AWG by 100 ft, even though 12 AWG stays legal on ampacity the whole way.

What size wire do I need for 50 amps?

8 AWG copper on 75 °C terminals: the 75 °C column gives exactly 50 A, so it is compliant with nothing to spare. On 60 °C terminals 8 AWG only reaches 40 A and you need 6 AWG. Aluminium needs 6 AWG, also exactly 50 A. Many electricians fit 6 AWG copper anyway, and distance justifies it — on a 240 V circuit, 8 AWG passes 3% drop only to about 60 ft, while 6 AWG reaches 100 ft at 2.0% and 4 AWG is required by 200 ft.

Why can I not use the 90 °C column?

Because of NEC 110.14(C), the terminal temperature limitation. The ampacity of a circuit is limited by the lowest-rated component in it, and that is almost always the terminals on your breaker or device — listed for 60 °C or 75 °C, effectively never 90 °C. THHN is a 90 °C wire, but landing it on a 75 °C terminal makes it a 75 °C installation. The 90 °C column is still useful: it is the correct starting point for applying derating factors.

Then why buy 90 °C wire at all?

Because derating starts from the 90 °C column. Six conductors in a hot attic get multiplied by an ambient factor and a fill factor, and starting from a larger number leaves you with more after both. In benign conditions 90 °C insulation buys nothing over 75 °C; in a derated installation it can save you a full conductor size.

What is voltage drop and does the NEC require me to limit it?

Voltage drop is the voltage lost in the conductor itself, proportional to current, length and resistance. The NEC does not require you to limit it — the 3% branch-circuit and 5% total figures appear in Informational Notes to 210.19(A) and 215.2(A), which are explicitly not enforceable. They are still good design. Excessive drop makes motors run hot, lights dim and heaters underperform, and none of that shows up in an inspection.

When does voltage drop start to matter more than ampacity?

Around 30 m or 100 ft for typical branch circuits, and sooner at 120 V than at 240 V. Below that, ampacity sets the size and voltage drop is comfortably inside 3%. Above it, the drop constraint takes over and grows linearly with distance while ampacity stays flat — which is why a detached garage so often needs wire two or three sizes larger than the load suggests.

What counts as a current-carrying conductor for derating?

Ungrounded (hot) conductors always count. Equipment grounding conductors never do. The neutral of a normal single-phase 120/240 V circuit does not count, because it carries only the unbalance between the two hots. But the neutral of a three-phase, four-wire wye circuit supplying nonlinear loads does count, per 310.15(E)(3), because triplen harmonics add rather than cancel in it.

Can I use aluminium wire?

Yes, and it is standard for larger feeders and service entrances because it is far cheaper per ampere. It needs roughly two sizes larger than copper for the same ampacity. Every termination must be listed for aluminium — look for AL or CO/ALR markings — and should be brushed and treated with an antioxidant compound. The problems with 1960s and 70s aluminium branch wiring were termination failures, not the metal.

How do I size wire for a motor?

Use the full-load current from NEC Table 430.250, not the motor nameplate. Branch-circuit conductors are sized at 125% of that table value per 430.22. Short-circuit protection is sized separately and much higher — up to 250% for an inverse-time breaker — because a motor draws six to eight times its running current on start.

Does stranded wire carry more current than solid?

No. Table 310.16 makes no distinction, and the ampacity is the same for a given AWG size either way. Stranded conductors are slightly larger in overall diameter and more flexible, which matters for conduit fill and for terminations, but not for how much current they may carry.

Sources and further reading

Last reviewed .

Related calculators