20 A kitchen circuit, 50 ft
The everyday case. Short run, so ampacity decides.
12 AWG — capped at 20 A by 240.4(D), not by the 30 A table entry
What size wire you need, from the load, the run length and the conditions — sized against both NEC ampacity and voltage drop, with the terminal temperature rule that stops 90 °C wire giving 90 °C ampacity.
In amperes. For a watts figure, divide by the voltage first.
Line-to-line for three phase. Higher voltage tolerates far longer runs.
A load expected to run for 3 hours or more is sized at 125% per 210.19(A)(1).
Distance from the panel to the load, not there and back.
The wire itself. This sets what you derate FROM, not what you may use.
Per 110.14(C). Modern breakers and panels are usually listed 75 °C — check the label.
In °C. Tables assume 30 °C. An attic in summer is 50 °C or more.
In the same raceway or cable. Grounds never count; see the notes on neutrals.
3% for a branch circuit, 5% for feeder plus branch combined — both recommendations, not rules.
12 AWG is set by ampacity. Ampacity alone would allow 12 AWG; voltage drop alone would need 14 AWG.
240.4(D) caps this size at 20 A regardless of the table. This is why 12 AWG THHN, which shows 30 A in the 90 °C column, still belongs on a 20 A breaker.
Voltage drop at 12 AWG: 3.86 V, 1.61% — arriving at 236.1 V. The 3% branch-circuit figure is a recommendation in an Informational Note, not an enforceable rule.
The everyday case. Short run, so ampacity decides.
12 AWG — capped at 20 A by 240.4(D), not by the 30 A table entry
A detached garage or workshop. Watch the answer jump two sizes for a load that has not changed.
8 AWG — voltage drop governs; ampacity would still permit 12 AWG
Where derating bites. Same load, much worse conditions.
6 AWG — ambient 0.82 × fill 0.80 = 0.656 on the 90 °C column. In benign conditions the same load takes 8 AWG
The usual choice for a long feeder. Compare against copper.
1 AWG aluminium — exactly two sizes above the 3 AWG copper the same feeder would take
Continuous loads are sized at 125%. This is why a 32 A charger needs a 40 A circuit.
40 A design current — 8 AWG on a 40 A breaker
When to use this: running a new circuit, feeding a detached building, adding an EV charger, or checking whether existing wire is adequate for a bigger load.
Two independent constraints decide the size, and they behave completely differently:
On a short run ampacity decides and voltage drop is irrelevant. Past roughly 100 ft they swap over, and from then on distance is the only thing that matters. A calculator that checks only ampacity will happily tell you 12 AWG is fine for a 20 A load 300 ft away. It is legal. It is also useless — the load will see about 19% less voltage than it should.
You buy THHN. Its jacket says 90 °C. Table 310.16 says 12 AWG copper carries 30 A in the 90 °C column. So a 30 A breaker, surely?
No. Two separate rules stop you, and both are easy to miss.
So 12 AWG THHN is a 30 A wire on paper, a 25 A wire after the terminal rule, and a 20 A wire after 240.4(D). The last number is the one you use.
Because derating starts from the 90 °C column. That is the one place the higher rating earns its money. Six conductors in a 50 °C attic get multiplied by 0.82 for ambient and 0.80 for conductor count — starting that multiplication from a bigger number leaves more at the end.
Worked through for 6 AWG copper: from the 90 °C column, 75 × 0.82 × 0.80 = 49.2 A. From the 75 °C column it would be 65 × 0.82 × 0.80 = 42.6 A. Same wire, same conditions, one full conductor size of difference — purely from which column you were entitled to start in.
The order matters and it is worth stating plainly: derate from the insulation column, then cap at the terminal column. Doing it the other way round is a common shortcut and it oversizes every derated run.
A 20 A load on a 240 V single-phase circuit, copper, 3% drop limit. The load never changes. Only the run does.
| One-way distance | Ampacity needs | Voltage drop needs | Answer | Drop at that size |
|---|---|---|---|---|
| 25 ft | 12 AWG | 14 AWG | 12 AWG | 0.80% |
| 50 ft | 12 AWG | 14 AWG | 12 AWG | 1.61% |
| 100 ft | 12 AWG | 10 AWG | 10 AWG | 2.03% |
| 150 ft | 12 AWG | 8 AWG | 8 AWG | 1.91% |
| 200 ft | 12 AWG | 8 AWG | 8 AWG | 2.55% |
| 300 ft | 12 AWG | 6 AWG | 6 AWG | 2.40% |
| 400 ft | 12 AWG | 4 AWG | 4 AWG | 2.01% |
The ampacity column never moves. The drop column climbs relentlessly. At 400 ft the same 20 A load wants 4 AWG — a conductor sized for a load four times larger, bought entirely to fight resistance.
Voltage is the cheapest lever here, because drop as a percentage scales with 1/V. That same 20 A at 400 ft needs 2 AWG at 120 V and 4 AWG at 240 V. Running a 240 V circuit and stepping down at the far end is often cheaper than the copper you would otherwise buy.
Copper, 75 °C terminals, 90 °C insulation, 30 °C ambient, three current-carrying conductors, non-continuous. The distance columns show where drop takes over.
| Circuit | Typical use | Ampacity only | At 50 ft | At 100 ft | At 200 ft |
|---|---|---|---|---|---|
| 15 A | Lighting, general receptacles | 14 AWG | 14 AWG | 12 AWG | 8 AWG |
| 20 A | Kitchen, bathroom, laundry receptacles | 12 AWG | 12 AWG | 10 AWG | 8 AWG |
| 30 A | Dryer, water heater, small subpanel | 10 AWG | 10 AWG | 8 AWG | 6 AWG |
| 40 A | Electric range, EV charger | 8 AWG | 8 AWG | 8 AWG | 4 AWG |
| 50 A | Range, welder, larger EV charger | 8 AWG | 8 AWG | 6 AWG | 4 AWG |
| 60 A | Subpanel, large HVAC | 6 AWG | 6 AWG | 6 AWG | 3 AWG |
| 100 A | Subpanel, small service | 3 AWG | 3 AWG | 3 AWG | 1 AWG |
| 150 A | Service entrance | 1/0 AWG | 1/0 AWG | 1/0 AWG | 1/0 AWG |
| 200 A | Standard residential service | 3/0 AWG | 3/0 AWG | 3/0 AWG | 3/0 AWG |
These are 240 V figures. At 120 V, halve the distance for the same drop — a 20 A 120 V circuit is already at 2.5% on 8 AWG by 100 ft.
Not more than three current-carrying conductors in a raceway or cable, 30 °C ambient. These are the values before any derating and before the terminal limit.
| Size | Copper | Aluminium | ||||
|---|---|---|---|---|---|---|
| 60 °C | 75 °C | 90 °C | 60 °C | 75 °C | 90 °C | |
| 14 AWG | 15 | 20 | 25 | — | — | — |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 30 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
Aluminium has no 14 AWG entry — the table starts at 12 AWG, and 14 AWG aluminium is not a branch-circuit conductor you can buy. Across the range, aluminium runs about two sizes behind copper for the same ampacity.
The table is built for 30 °C. Anything hotter costs you ampacity, and the colder-rated the insulation, the harder it is punished.
| Ambient | 60 °C column | 75 °C column | 90 °C column |
|---|---|---|---|
| 25 °C | 1.08 | 1.05 | 1.04 |
| 30 °C | 1.00 | 1.00 | 1.00 |
| 35 °C | 0.91 | 0.94 | 0.96 |
| 40 °C | 0.82 | 0.88 | 0.91 |
| 45 °C | 0.71 | 0.82 | 0.87 |
| 50 °C | 0.58 | 0.75 | 0.82 |
| 55 °C | 0.41 | 0.67 | 0.76 |
A dash in the published table means the conductor may not be used at that ambient at all — shown here as "not permitted" rather than quietly treated as no correction, which is the dangerous reading. Note 60 °C wire is finished at 55 °C ambient while 90 °C wire keeps going to 85 °C.
More than three current-carrying conductors sharing a raceway and they cook each other.
| Current-carrying conductors | Adjustment |
|---|---|
| 3 | 100% |
| 4 | 80% |
| 6 | 80% |
| 7 | 70% |
| 10 | 50% |
| 20 | 50% |
| 21 | 45% |
| 41 | 35% |
What counts is the subtle part. Ungrounded conductors always count. Equipment grounding conductors never do. The neutral of an ordinary 120/240 V single-phase circuit does not count, because it only carries the unbalance between the two hots. But the neutral of a three-phase four-wire wye circuit feeding nonlinear loads — LED drivers, computer supplies, VFDs — does count under 310.15(E)(3), because triplen harmonics add in the neutral instead of cancelling. That neutral can carry more current than any phase.
The 3% branch-circuit and 5% combined figures live in Informational Notes to 210.19(A) and 215.2(A). Informational Notes are explicitly not enforceable requirements. No inspector will fail you for voltage drop on a dwelling branch circuit.
They are still worth designing to, because the failures are real and diffuse:
This calculator figures drop from conductor resistivity at 75 °C rather than the K-constant shortcut, so it agrees with our voltage drop calculator exactly. That works out to K ≈ 12.6 for copper against the textbook 12.9 — about 2%, and in the conservative direction against most published tables.
Once you have a size, check it fits: our conduit fill calculator works to NEC Chapter 9, and the load calculator works out the service size those feeders have to come from.
In amperes. If you have a wattage, divide by the voltage first. For motors use the table FLC from NEC 430.250, not the nameplate current.
Anything expected to run for three hours or more — EV charging, electric heating, most commercial lighting. The conductor is then sized to 125% of the load.
From the panel to the load, measured along the actual cable path rather than in a straight line. The calculator handles the return conductor itself.
Ambient temperature and the number of current-carrying conductors sharing the raceway. Both derate the conductor, and both are routinely left out of hand calculations.
Look at the label on your breaker and panel. Most modern equipment is listed for 75 °C; older or smaller equipment may be 60 °C only. This caps your ampacity regardless of the wire you buy.
The result shows the size ampacity needs and the size voltage drop needs. On a short run they differ and ampacity wins; past roughly 100 ft the drop takes over.
12 AWG copper for a typical run. 14 AWG is limited to 15 A by NEC 240.4(D), so it cannot serve a 20 A circuit no matter what its insulation is rated for. Distance changes the answer fast at 120 V: keeping drop under 3% needs 10 AWG by 50 ft and 8 AWG by 100 ft, even though 12 AWG stays legal on ampacity the whole way.
8 AWG copper on 75 °C terminals: the 75 °C column gives exactly 50 A, so it is compliant with nothing to spare. On 60 °C terminals 8 AWG only reaches 40 A and you need 6 AWG. Aluminium needs 6 AWG, also exactly 50 A. Many electricians fit 6 AWG copper anyway, and distance justifies it — on a 240 V circuit, 8 AWG passes 3% drop only to about 60 ft, while 6 AWG reaches 100 ft at 2.0% and 4 AWG is required by 200 ft.
Because of NEC 110.14(C), the terminal temperature limitation. The ampacity of a circuit is limited by the lowest-rated component in it, and that is almost always the terminals on your breaker or device — listed for 60 °C or 75 °C, effectively never 90 °C. THHN is a 90 °C wire, but landing it on a 75 °C terminal makes it a 75 °C installation. The 90 °C column is still useful: it is the correct starting point for applying derating factors.
Because derating starts from the 90 °C column. Six conductors in a hot attic get multiplied by an ambient factor and a fill factor, and starting from a larger number leaves you with more after both. In benign conditions 90 °C insulation buys nothing over 75 °C; in a derated installation it can save you a full conductor size.
Voltage drop is the voltage lost in the conductor itself, proportional to current, length and resistance. The NEC does not require you to limit it — the 3% branch-circuit and 5% total figures appear in Informational Notes to 210.19(A) and 215.2(A), which are explicitly not enforceable. They are still good design. Excessive drop makes motors run hot, lights dim and heaters underperform, and none of that shows up in an inspection.
Around 30 m or 100 ft for typical branch circuits, and sooner at 120 V than at 240 V. Below that, ampacity sets the size and voltage drop is comfortably inside 3%. Above it, the drop constraint takes over and grows linearly with distance while ampacity stays flat — which is why a detached garage so often needs wire two or three sizes larger than the load suggests.
Ungrounded (hot) conductors always count. Equipment grounding conductors never do. The neutral of a normal single-phase 120/240 V circuit does not count, because it carries only the unbalance between the two hots. But the neutral of a three-phase, four-wire wye circuit supplying nonlinear loads does count, per 310.15(E)(3), because triplen harmonics add rather than cancel in it.
Yes, and it is standard for larger feeders and service entrances because it is far cheaper per ampere. It needs roughly two sizes larger than copper for the same ampacity. Every termination must be listed for aluminium — look for AL or CO/ALR markings — and should be brushed and treated with an antioxidant compound. The problems with 1960s and 70s aluminium branch wiring were termination failures, not the metal.
Use the full-load current from NEC Table 430.250, not the motor nameplate. Branch-circuit conductors are sized at 125% of that table value per 430.22. Short-circuit protection is sized separately and much higher — up to 250% for an inverse-time breaker — because a motor draws six to eight times its running current on start.
No. Table 310.16 makes no distinction, and the ampacity is the same for a given AWG size either way. Stranded conductors are slightly larger in overall diameter and more flexible, which matters for conduit fill and for terminations, but not for how much current they may carry.
Last reviewed .
Diameter, cross-section, resistance and current rating for any AWG size — with separate free-air and in-conduit ampacity, because they differ by a factor of two.
ΔVVoltage drop for DC, single-phase and three-phase runs in copper or aluminium, sized in mm² or AWG, checked against IEC and NEC limits.
40%How many conductors fit in a conduit, and what size you need. EMT, IMC, RMC and PVC with the real Chapter 9 table areas — including the 31% rule that catches people out.
kVASize a house service the way an electrician does: NEC Article 220 standard calculation, with the demand factors that stop a 40 kW house needing a 400 A service.