Garage supply — 20 A over 30 m
A classic sub-main run. Long enough that voltage drop, not current rating, decides the cable size.
5.17 V drop, 2.25% — comfortably inside the 5% limit
Voltage drop for DC, single-phase and three-phase runs in copper or aluminium, sized in mm² or AWG, checked against IEC and NEC limits.
The design current the cable will actually carry.
Distance from source to load. The return conductor is accounted for automatically.
Cables run hot under load. 70 °C is a realistic figure for a fully loaded PVC cable.
2.25% is within the 5% limit, with 2.75 percentage points of margin.
The cable is dissipating 103 W as heat. Over a year of continuous operation that is 906 kWh wasted — often enough to pay for the larger cable.
A classic sub-main run. Long enough that voltage drop, not current rating, decides the cable size.
5.17 V drop, 2.25% — comfortably inside the 5% limit
2.5 mm² is rated for 20 A in free air, so it passes on current. See what it does to the drop.
8.28 V, 3.6% — passes 5% but fails a 3% lighting limit
Three-phase uses √3 rather than 2, so the same conductor goes further than a single-phase run would.
4.48 V, 1.12% — plenty of margin
Low-voltage DC is unforgiving. The same absolute drop is a far bigger percentage.
1.38 V — 11.5%, badly over limit despite a short run
When to use this: sizing a sub-main to an outbuilding, running power to a machine at the far end of a workshop, wiring a 12 V solar or automotive system, or working out why the motor at the end of a long run keeps tripping on undervoltage.
Every conductor has resistance. Push current through it and some of the supply voltage is consumed by the cable itself rather than delivered to the load. The formula is just Ohm’s law applied to the cable:
ΔV = 2 × L × I × ρ / A (DC and single-phase)ΔV = √3 × L × I × ρ / A (balanced three-phase)
L is the one-way run in metres, I the current in amps, ρ the resistivity in Ω·mm²/m, and A the cross-section in mm². The factor of 2 is there because the current has to come back — the loop is twice the cable length.
Three-phase uses √3 because in a balanced system the three phase currents are 120° apart and largely cancel in the return path. The practical result: the same cable carries the same current with about 13% less drop on three-phase than single-phase.
| Standard | Lighting | Other loads | Measured from |
|---|---|---|---|
| IEC 60364-5-52 Annex G | 3% | 5% | Origin of the installation |
| NEC 210.19(A) / 215.2(A) | 3% branch, 5% feeder + branch total | Service entrance | |
Neither figure is a hard legal limit in most jurisdictions — both appear as recommendations or informational notes. In practice they are what an inspector expects and what equipment manufacturers assume, so treat them as binding unless you have a specific reason not to.
Lighting gets the tighter limit because incandescent output falls off sharply with voltage, and because flicker from voltage sag on other circuits is most visible in lighting.
The limit is a percentage, and that is what makes low-voltage DC so unforgiving. Consider the same 1 V of drop:
| Supply | 1 V drop is | Verdict |
|---|---|---|
| 400 V three-phase | 0.25% | Irrelevant |
| 230 V single-phase | 0.43% | Irrelevant |
| 48 V DC | 2.1% | Noticeable |
| 12 V DC | 8.3% | Over limit |
It compounds, too. For the same power, a 12 V system carries roughly 19 times the current of a 230 V one, and drop is proportional to current. This is why a 12 V solar installation uses conductors that look absurd for the wattage involved, and why the industry keeps moving to 48 V wherever it can.
Copper resistance rises about 0.393% per kelvin. The 20 °C figure in most tables is a reference condition, not an operating one:
| Conductor temperature | Resistance vs 20 °C | Typical situation |
|---|---|---|
| 20 °C | 100% | Reference / unloaded |
| 50 °C | +12% | Moderately loaded |
| 70 °C | +20% | PVC cable at full rating |
| 90 °C | +28% | XLPE cable at full rating |
A design that lands at exactly 5% at 20 °C is really at 6% once the cable warms up. If you are close to the limit, run the calculation at the cable’s rated temperature rather than the reference one.
ΔV = 2 × 30 × 20 × 0.017241 / 4 = 5.17 V5.17 / 230 = 2.25%
Inside the 5% limit with room to spare. Note the cable is also dissipating 20 × 5.17 = 103 W as heat when fully loaded — over a year of continuous use that is 900 kWh, which is usually a stronger argument for the larger cable than the drop limit is.
ΔV = 2 × 30 × 20 × 0.017241 / 2.5 = 8.28 V = 3.6%
2.5 mm² is rated for 20 A in free air, so it passes on current-carrying capacity. It passes a 5% limit too. But it fails a 3% lighting limit, and it wastes 60% more energy as heat. This is the case where current rating and voltage drop give different answers — and voltage drop is the one that should decide.
ΔV = 2 × 10 × 10 × 0.017241 / 2.5 = 1.38 V = 11.5%
Badly over limit despite a short run and a cable size that would be generous at 230 V. To hit 5% you would need about 5.8 mm² — call it 6 mm², which is more than twice the copper for a tenth of the power. That is the price of low voltage.
Aluminium has about 61% the conductivity of copper, so it needs roughly 1.6× the cross-section for the same drop. Against that, it is far cheaper and much lighter, which is why service entrances and large feeders are routinely aluminium.
The real difficulties are mechanical rather than electrical. Aluminium creeps under sustained pressure, so terminations loosen over time unless they are torque-rated and listed for aluminium. It also forms an insulating oxide layer almost instantly on exposure to air, so joints normally need an anti-oxidant compound. Neither issue is a reason to avoid it — they are reasons to terminate it properly.
Cable sizing has two independent constraints, and you take whichever demands more copper:
On short runs the current rating almost always decides. Past roughly 20–30 m, voltage drop takes over and frequently demands a cable one or two sizes larger than the current rating alone would suggest.
DC and single-phase AC both use a factor of 2 for the return conductor. Balanced three-phase uses √3.
Use the one-way distance from source to load — the return path is included automatically.
Switch between mm² and AWG as needed. Aluminium needs roughly 1.6× the cross-section of copper for the same drop.
A cable at its 70 °C rating has about 20% more resistance than at 20 °C. Designing at 20 °C understates the drop.
If the drop exceeds the limit, the calculator tells you the minimum cross-section that would meet it.
For DC and single-phase AC, ΔV = 2 × L × I × ρ / A, where L is the one-way length in metres, I the current in amps, ρ the resistivity in Ω·mm²/m, and A the cross-section in mm². The factor of 2 accounts for the return conductor. For balanced three-phase, the factor is √3 instead of 2.
IEC 60364-5-52 Annex G recommends 3% for lighting circuits and 5% for other uses, measured from the origin of the installation. The NEC gives the same figures as informational notes in 210.19(A) and 215.2(A) — 3% on a branch circuit and 5% for feeder plus branch combined. Neither is a hard legal limit in most jurisdictions, but both are what inspectors expect.
In a balanced three-phase system the three phase currents are 120° apart and largely cancel in the return path, so there is no full return conductor to account for. The line-to-line voltage relationship introduces the √3. The practical effect is that a three-phase run of the same cable has about 13% less drop than the single-phase equivalent.
Significantly. Copper resistance rises about 0.393% per kelvin. A cable at its 70 °C rating has roughly 20% more resistance than at the 20 °C reference, and one at 90 °C about 28% more. Calculating at 20 °C for a fully loaded cable understates the real drop.
Four options, in rough order of cost-effectiveness: increase the conductor cross-section, shorten the run, raise the supply voltage, or reduce the load current. Doubling the cross-section halves the drop. Raising the voltage helps twice over, since both the absolute drop falls and the percentage is taken against a larger number.
Because the limit is a percentage. A 1 V drop on a 230 V supply is 0.43%; the same 1 V on a 12 V supply is 8.3%. Low-voltage systems also carry more current for the same power, and drop is proportional to current — so the effect compounds. This is why 12 V solar and automotive installations use conductors that look absurdly large for the power involved.
Not inherently — it is standard for large feeders and service entrances. It has about 61% the conductivity of copper, so it needs roughly 1.6× the cross-section for the same drop. The real issues are mechanical: aluminium creeps under pressure, so terminations must be torque-rated and listed for aluminium, and an anti-oxidant compound is normally required.
Both, and take whichever is larger. Current rating protects the cable from overheating; voltage drop protects the load from being undersupplied. On short runs the current rating usually decides. On long runs voltage drop almost always decides, and by a wide margin.
Last reviewed .
Diameter, cross-section, resistance and current rating for any AWG size — with separate free-air and in-conduit ampacity, because they differ by a factor of two.
WPower from any two of voltage, current and resistance — then energy in kWh and what it costs to run.
ΩSolve for voltage, current, resistance or power. Get all four values at once, plus the resistor wattage you actually need.
R1R2Calculate output voltage, ratio, current and output impedance — with the loading effect built in, not hidden on another page.