Cable Voltage Drop Calculator

Voltage drop for DC, single-phase and three-phase runs in copper or aluminium, sized in mm² or AWG, checked against IEC and NEC limits.

Inputs

System
V

A

The design current the cable will actually carry.

m

Distance from source to load. The return conductor is accounted for automatically.

Conductor
Size by
°C

Cables run hot under load. 70 °C is a realistic figure for a fully loaded PVC cable.

Permitted drop

Results

Voltage drop5.172 VΔV = k·L·I·ρ/A
Drop
2.249 %
Voltage at load
224.8 V
Loop resistance
258.6 mΩ
Power lost in cable
103.4 W

2.25% is within the 5% limit, with 2.75 percentage points of margin.

The cable is dissipating 103 W as heat. Over a year of continuous operation that is 906 kWh wasted — often enough to pay for the larger cable.

Diagram

Cable run from supply to loadA 30 m run carrying 20 A drops 5.17 V, leaving 225 V at the load.Supply230 VLoad225 V30 m one way20 A5.17 V (2.25%)103 W lost as heat

Worked examples

Garage supply — 20 A over 30 m

A classic sub-main run. Long enough that voltage drop, not current rating, decides the cable size.

5.17 V drop, 2.25% — comfortably inside the 5% limit

The same run in 2.5 mm²

2.5 mm² is rated for 20 A in free air, so it passes on current. See what it does to the drop.

8.28 V, 3.6% — passes 5% but fails a 3% lighting limit

Three-phase motor, 30 A over 50 m

Three-phase uses √3 rather than 2, so the same conductor goes further than a single-phase run would.

4.48 V, 1.12% — plenty of margin

12 V DC over 10 m — where drop really bites

Low-voltage DC is unforgiving. The same absolute drop is a far bigger percentage.

1.38 V — 11.5%, badly over limit despite a short run

How cable voltage drop works

When to use this: sizing a sub-main to an outbuilding, running power to a machine at the far end of a workshop, wiring a 12 V solar or automotive system, or working out why the motor at the end of a long run keeps tripping on undervoltage.

Every conductor has resistance. Push current through it and some of the supply voltage is consumed by the cable itself rather than delivered to the load. The formula is just Ohm’s law applied to the cable:

ΔV = 2 × L × I × ρ / A  (DC and single-phase)
ΔV = √3 × L × I × ρ / A  (balanced three-phase)

L is the one-way run in metres, I the current in amps, ρ the resistivity in Ω·mm²/m, and A the cross-section in mm². The factor of 2 is there because the current has to come back — the loop is twice the cable length.

Three-phase uses √3 because in a balanced system the three phase currents are 120° apart and largely cancel in the return path. The practical result: the same cable carries the same current with about 13% less drop on three-phase than single-phase.

The limits

StandardLightingOther loadsMeasured from
IEC 60364-5-52 Annex G3%5%Origin of the installation
NEC 210.19(A) / 215.2(A)3% branch, 5% feeder + branch totalService entrance

Neither figure is a hard legal limit in most jurisdictions — both appear as recommendations or informational notes. In practice they are what an inspector expects and what equipment manufacturers assume, so treat them as binding unless you have a specific reason not to.

Lighting gets the tighter limit because incandescent output falls off sharply with voltage, and because flicker from voltage sag on other circuits is most visible in lighting.

Why low-voltage systems suffer most

The limit is a percentage, and that is what makes low-voltage DC so unforgiving. Consider the same 1 V of drop:

Supply1 V drop isVerdict
400 V three-phase0.25%Irrelevant
230 V single-phase0.43%Irrelevant
48 V DC2.1%Noticeable
12 V DC8.3%Over limit

It compounds, too. For the same power, a 12 V system carries roughly 19 times the current of a 230 V one, and drop is proportional to current. This is why a 12 V solar installation uses conductors that look absurd for the wattage involved, and why the industry keeps moving to 48 V wherever it can.

Temperature matters more than people expect

Copper resistance rises about 0.393% per kelvin. The 20 °C figure in most tables is a reference condition, not an operating one:

Conductor temperatureResistance vs 20 °CTypical situation
20 °C100%Reference / unloaded
50 °C+12%Moderately loaded
70 °C+20%PVC cable at full rating
90 °C+28%XLPE cable at full rating

A design that lands at exactly 5% at 20 °C is really at 6% once the cable warms up. If you are close to the limit, run the calculation at the cable’s rated temperature rather than the reference one.

Worked examples

Garage sub-main: 20 A over 30 m

ΔV = 2 × 30 × 20 × 0.017241 / 4 = 5.17 V
5.17 / 230 = 2.25%

Inside the 5% limit with room to spare. Note the cable is also dissipating 20 × 5.17 = 103 W as heat when fully loaded — over a year of continuous use that is 900 kWh, which is usually a stronger argument for the larger cable than the drop limit is.

The same run in 2.5 mm²

ΔV = 2 × 30 × 20 × 0.017241 / 2.5 = 8.28 V = 3.6%

2.5 mm² is rated for 20 A in free air, so it passes on current-carrying capacity. It passes a 5% limit too. But it fails a 3% lighting limit, and it wastes 60% more energy as heat. This is the case where current rating and voltage drop give different answers — and voltage drop is the one that should decide.

12 V DC over 10 m at 10 A

ΔV = 2 × 10 × 10 × 0.017241 / 2.5 = 1.38 V = 11.5%

Badly over limit despite a short run and a cable size that would be generous at 230 V. To hit 5% you would need about 5.8 mm² — call it 6 mm², which is more than twice the copper for a tenth of the power. That is the price of low voltage.

Copper or aluminium

Aluminium has about 61% the conductivity of copper, so it needs roughly 1.6× the cross-section for the same drop. Against that, it is far cheaper and much lighter, which is why service entrances and large feeders are routinely aluminium.

The real difficulties are mechanical rather than electrical. Aluminium creeps under sustained pressure, so terminations loosen over time unless they are torque-rated and listed for aluminium. It also forms an insulating oxide layer almost instantly on exposure to air, so joints normally need an anti-oxidant compound. Neither issue is a reason to avoid it — they are reasons to terminate it properly.

Reducing voltage drop

  • Larger cross-section. Drop is inversely proportional to area, so doubling the cross-section halves the drop. Usually the first and simplest fix.
  • Shorter run. Drop is directly proportional to length. Moving a distribution board closer to the load is often cheaper than upsizing a long cable.
  • Higher voltage. This helps twice — the current falls for the same power, and the percentage is taken against a larger number. Going from 12 V to 24 V cuts the percentage drop by a factor of four for the same load.
  • Split the load. Two circuits each carrying half the current have half the drop each, for the same total copper.

Size for both current and drop

Cable sizing has two independent constraints, and you take whichever demands more copper:

  • Current-carrying capacity protects the cable. Exceed it and the insulation overheats and eventually fails. This is a safety limit.
  • Voltage drop protects the load. Exceed it and equipment runs undervoltage — motors draw more current and run hot, electronics reset, lighting dims. This is a performance limit.

On short runs the current rating almost always decides. Past roughly 20–30 m, voltage drop takes over and frequently demands a cable one or two sizes larger than the current rating alone would suggest.

How to use this calculator

  1. Pick the system type

    DC and single-phase AC both use a factor of 2 for the return conductor. Balanced three-phase uses √3.

  2. Enter the load and the run length

    Use the one-way distance from source to load — the return path is included automatically.

  3. Choose the conductor and size

    Switch between mm² and AWG as needed. Aluminium needs roughly 1.6× the cross-section of copper for the same drop.

  4. Set a realistic temperature

    A cable at its 70 °C rating has about 20% more resistance than at 20 °C. Designing at 20 °C understates the drop.

  5. Check against the limit

    If the drop exceeds the limit, the calculator tells you the minimum cross-section that would meet it.

Frequently asked questions

What is the voltage drop formula?

For DC and single-phase AC, ΔV = 2 × L × I × ρ / A, where L is the one-way length in metres, I the current in amps, ρ the resistivity in Ω·mm²/m, and A the cross-section in mm². The factor of 2 accounts for the return conductor. For balanced three-phase, the factor is √3 instead of 2.

What is the maximum allowable voltage drop?

IEC 60364-5-52 Annex G recommends 3% for lighting circuits and 5% for other uses, measured from the origin of the installation. The NEC gives the same figures as informational notes in 210.19(A) and 215.2(A) — 3% on a branch circuit and 5% for feeder plus branch combined. Neither is a hard legal limit in most jurisdictions, but both are what inspectors expect.

Why does three-phase use √3 instead of 2?

In a balanced three-phase system the three phase currents are 120° apart and largely cancel in the return path, so there is no full return conductor to account for. The line-to-line voltage relationship introduces the √3. The practical effect is that a three-phase run of the same cable has about 13% less drop than the single-phase equivalent.

Does cable temperature affect voltage drop?

Significantly. Copper resistance rises about 0.393% per kelvin. A cable at its 70 °C rating has roughly 20% more resistance than at the 20 °C reference, and one at 90 °C about 28% more. Calculating at 20 °C for a fully loaded cable understates the real drop.

How do I reduce voltage drop?

Four options, in rough order of cost-effectiveness: increase the conductor cross-section, shorten the run, raise the supply voltage, or reduce the load current. Doubling the cross-section halves the drop. Raising the voltage helps twice over, since both the absolute drop falls and the percentage is taken against a larger number.

Why is voltage drop worse on low-voltage DC?

Because the limit is a percentage. A 1 V drop on a 230 V supply is 0.43%; the same 1 V on a 12 V supply is 8.3%. Low-voltage systems also carry more current for the same power, and drop is proportional to current — so the effect compounds. This is why 12 V solar and automotive installations use conductors that look absurdly large for the power involved.

Is aluminium cable a problem?

Not inherently — it is standard for large feeders and service entrances. It has about 61% the conductivity of copper, so it needs roughly 1.6× the cross-section for the same drop. The real issues are mechanical: aluminium creeps under pressure, so terminations must be torque-rated and listed for aluminium, and an anti-oxidant compound is normally required.

Should I size a cable for current rating or voltage drop?

Both, and take whichever is larger. Current rating protects the cable from overheating; voltage drop protects the load from being undersupplied. On short runs the current rating usually decides. On long runs voltage drop almost always decides, and by a wide margin.

Sources and further reading

Last reviewed .

Related calculators