Bare essentials — fridge, lights, phones
Riding out a short outage. The fridge surge sets the size on its own.
2,000 W — 900 W running, but 1,900 W the moment the compressor kicks in
What size generator you actually need — running watts plus the largest single starting surge, derated for altitude and heat. Not the sum of every surge, which is how most calculators oversize you.
200 W running each, but roughly 1,200 W to start the compressor.
Usually the single biggest surge in a house, and usually what sets the answer.
Resistive, so no surge — but 4,500 W continuous is a lot of generator.
Total watts. LED lighting throughout a house is often under 300 W.
Microwave, kettle, toaster. Only count what runs at the same time.
Router, TV, laptops, phone charging.
Anything else running continuously. Add surge separately if it has a motor.
Feet above sea level. Engines lose about 3% per 1,000 ft above 1,000 ft.
°F. Above 85 °F the engine loses roughly 2% per 10 °F.
Gallons. Set to 0 to skip the runtime estimate.
Peak demand is 900 W running plus 1,000 W of surge from the refrigerator or freezer 1 — the largest single starting load, and the only one that counts.
Adding every surge together would demand 1,900 W instead of 1,900 W. Motors do not start simultaneously, so that figure buys a generator you do not need.
Continuous load is 45% of the recommended generator, which is in the healthy 25–80% band.
At this load the engine burns about 0.19 gal/h, so a 5 gal tank runs roughly 26.7 hours. Consumption is close to linear in load — running at half output does not halve the burn, because idle overhead is fixed.
Riding out a short outage. The fridge surge sets the size on its own.
2,000 W — 900 W running, but 1,900 W the moment the compressor kicks in
Furnace blower and well pump. No air conditioning, so the well pump governs.
6,500 W — the 3/4 HP well pump contributes 3,000 W of surge
The air conditioner dominates everything else on the list.
The AC surge alone is 7,000 W — more than every other load combined
One cheap module against a generator two sizes larger. Compare with the preset above.
Compressor inrush drops by 65% and the generator drops with it
Same loads, thinner air. The label on the box is a sea-level figure.
21% derating — you need a fifth more generator than the load suggests
When to use this: buying a portable generator for outages, specifying a standby unit, sizing for an RV or a jobsite, or working out whether the generator you already own will carry what you need.
A generator has to survive the instant a motor starts. Everything else about sizing follows from that, and it means two numbers matter rather than one:
Peak demand = every running watt + the surge of ONE motor.
Not the sum of every surge. Motors do not start together — you start them one at a time, and everything else is already running when they do. This one rule separates a sensible answer from an expensive one.
A house with four motor loads, worked through:
| Load | Running W | Starting W | Surge above running |
|---|---|---|---|
| Refrigerator or freezer | 200 | 1,200 | 1,000 |
| Well pump, 1 HP | 2,000 | 6,000 | 4,000 |
| Central AC, 3 ton | 3,500 | 10,500 | 7,000 |
| Furnace blower, 1/2 HP | 800 | 2,350 | 1,550 |
| Total running | 6,500 | ||
| Method | Peak demand | Generator needed |
|---|---|---|
| Ignore surge entirely | 6,500 W | 6,500 W — stalls when the AC starts |
| Running + largest single surge | 13,500 W | 14,000 W |
| Sum every surge | 20,050 W | 22,000 W — 57% more machine for nothing |
The correct method asks for a 14,000 W generator. Summing the surges asks for 22,000 W — thousands more, heavier, thirstier, and no more capable.
Note also that the surge counted is the increment above running, not the whole starting figure. When the compressor starts it is about to contribute its running watts anyway; adding the full starting number on top of the running total double-counts it.
| Load | Running W | Starting W | Ratio |
|---|---|---|---|
| Refrigerator or freezer | 200 | 1,200 | 6.0× |
| Furnace blower, 1/3 HP | 600 | 1,800 | 3.0× |
| Furnace blower, 1/2 HP | 800 | 2,350 | 2.9× |
| Furnace blower, 3/4 HP | 1,200 | 3,500 | 2.9× |
| Furnace blower, ECM variable speed | 500 | 600 | 1.2× |
| Sump pump, 1/3 HP | 600 | 1,800 | 3.0× |
| Sump pump, 1/2 HP | 875 | 2,625 | 3.0× |
| Well pump, 1/2 HP | 1,000 | 3,000 | 3.0× |
| Well pump, 3/4 HP | 1,500 | 4,500 | 3.0× |
| Well pump, 1 HP | 2,000 | 6,000 | 3.0× |
| Well pump, 1.5 HP | 2,800 | 8,400 | 3.0× |
| Central AC, 2 ton | 2,400 | 7,200 | 3.0× |
| Central AC, 3 ton | 3,500 | 10,500 | 3.0× |
| Central AC, 4 ton | 4,800 | 13,500 | 2.8× |
| Central AC, 5 ton | 6,000 | 16,500 | 2.8× |
| Window air conditioner | 1,200 | 3,600 | 3.0× |
| Electric water heater | 4,500 | no surge | 1.0× |
Two things stand out. The refrigerator has the highest ratio on the list at 6× — but it is 6× a very small number, so it only matters when it is the only motor you have. The water heater draws 4,500 W continuously and surges not at all, because a resistance element has no inertia to overcome.
The ECM furnace blower is worth noticing too. A conventional blower jumps to three times running; an ECM variable-speed motor ramps, so its surge is negligible. Where you have the choice, that difference can decide the generator.
Our appliance wattage chart carries running, surge and standby figures for around 58 household appliances if your list is longer than the worksheet above.
On almost any house with central air conditioning, the compressor surge is what sets the generator size — it is frequently larger than every other load added together. A soft start module ramps the compressor over a second or two instead of connecting it across the line, cutting inrush by roughly 65%.
On the four-load example above, that takes peak demand from 13,500 W to 10,500 W, and the generator from 14,000 W to 11,000 W. The module costs a small fraction of the difference between those two machines, which makes it one of the few genuinely free lunches in this area.
Engines are rated at sea level in mild conditions. Thin air means less oxygen per cylinder charge and less power; heat does the same. Neither appears on the box.
| Altitude | 77 °F | 85 °F | 95 °F | 105 °F |
|---|---|---|---|---|
| 0 ft | 100% | 100% | 98% (−2%) | 96% (−4%) |
| 2,000 ft | 97% (−3%) | 97% (−3%) | 95% (−5%) | 93% (−7%) |
| 4,000 ft | 91% (−9%) | 91% (−9%) | 89% (−11%) | 87% (−13%) |
| 6,000 ft | 85% (−15%) | 85% (−15%) | 83% (−17%) | 81% (−19%) |
| 8,000 ft | 79% (−21%) | 79% (−21%) | 77% (−23%) | 75% (−25%) |
| 10,000 ft | 73% (−27%) | 73% (−27%) | 71% (−29%) | 69% (−31%) |
At 8,000 ft on a 95 °F day a generator delivers 77% of its rating — a 7,500 W machine gives about 5,775 W. If you live somewhere high, size the load first and then divide by the derating factor, which is what this calculator does.
Sizing to exactly your peak leaves nothing in reserve. Aim to run continuously at 50–75% of the rating.
The summer example — fridge, blower, 3-ton AC and a 3/4 HP well pump at 95 °F — comes out at a 14,000 W generator running at 48% continuous load, which is squarely in the band.
Consumption is close to linear in load above about a quarter output, with a fixed idle component underneath. Running at half load does not halve the burn.
| Continuous load | Petrol, gal/h | Propane, gal/h | Diesel, gal/h |
|---|---|---|---|
| 1,000 W | 0.20 | 0.28 | 0.14 |
| 2,500 W | 0.31 | 0.43 | 0.23 |
| 5,000 W | 0.49 | 0.70 | 0.36 |
| 7,500 W | 0.68 | 0.96 | 0.50 |
| 10,000 W | 0.87 | 1.22 | 0.64 |
Propane needs roughly 40% more volume for the same energy, but it stores indefinitely without degrading — which is why standby installations favour it and why a jerrycan of petrol in the garage is a worse plan than it looks. Diesel is the most efficient per gallon and the least tolerant of light loading.
A generator feeding house circuits must go through a transfer switch or an interlock kit, installed by a qualified electrician. Back-feeding through a dryer outlet — the so-called suicide cord — energises the utility lines outside your house and can kill a lineworker restoring power. It is also illegal essentially everywhere.
A transfer switch is not only a safety device. It is what lets you sequence loads, which is precisely the assumption the surge rule rests on: start the largest motor first, or bring circuits up one at a time, and your peak stays where this calculator put it.
The generator's output circuit needs sizing like any other. Our wire size calculator handles the run from generator to transfer switch, and the load calculator works out the whole-house demand if you are considering a standby unit that carries everything.
Not everything you own — everything you need running simultaneously during an outage. A generator sized for the whole house is usually a generator sized for loads you would never run together.
Refrigerators, well pumps, sump pumps, furnace blowers and air conditioners all draw far more to start than to run. Resistive loads — heaters, kettles, incandescent lamps, water heaters — do not.
Peak demand is every running watt plus the surge of one motor, because they do not start together. This is the step most calculators get wrong in one direction or the other.
Generators are rated at sea level in mild conditions. At 6,000 ft on a hot day you have about four fifths of the label, and nothing on the label says so.
Aim to run at 50–75% of the rating. Above 80% there is no reserve for the next motor start; below 25% a diesel engine wet-stacks.
For essentials — fridge, lights, phones, a modest amount of electronics — around 2,000 to 3,500 W. Add a furnace blower and well pump and you are at 6,000 to 8,000 W. Add central air conditioning and you are at 10,000 to 14,000 W, because the compressor surge alone can exceed everything else combined. The honest question is not "how big is my house" but "what must run at the same time".
Running watts is the continuous draw once a device is up to speed. Starting watts, also called surge or peak watts, is the momentary draw while a motor overcomes inertia — typically three times running for a capacitor-start motor and up to six times for a split-phase one. It lasts a second or two, but the generator has to supply it or the motor stalls and the breaker trips.
No, and this is the single most common sizing error. Motors do not start simultaneously — you start them one at a time, and everything else is already running when they do. The correct peak is all running watts plus the largest single surge. Summing every surge can demand half again more generator than you need: a house with a fridge, a well pump, a 3-ton AC and a blower needs 13,500 W by the correct method and 20,050 W by the wrong one, which is a 14 kW machine against a 22 kW one.
Usually not the way you would assume. Portable generators are commonly marketed on their peak or starting figure, with the running figure in smaller print — a "5,500 W" generator may deliver 4,500 W continuously. Size against the running rating and treat the peak as headroom for motor starts, not as capacity you can use.
Less air means less oxygen per cylinder charge, so the engine makes less power. The rule of thumb for naturally aspirated engines is a 3% loss per 1,000 ft above 1,000 ft. At 8,000 ft that is 21% — a 7,500 W generator delivers under 6,000 W. Heat compounds it at roughly 2% per 10 °F above 85 °F. Neither derating appears on the box.
A soft start module ramps an air-conditioning compressor up over a second or two instead of connecting it across the line, cutting inrush by around 65%. Because the AC surge is usually what sets the generator size, fitting one often drops the requirement by a full size or two. The module costs a fraction of the difference between those generators, which makes it one of the few genuinely free lunches in this area.
Between about 50% and 75% of its rating. Above 80% there is no reserve for the next motor start and the engine runs hot with no margin for error. Below about 25% a diesel wet-stacks: unburnt fuel accumulates and glazes the cylinder bores, which shortens engine life. Petrol engines tolerate light loading better, but there is no benefit to buying capacity you never use.
Fuel burn is close to linear in load above about a quarter output, with a fixed idle component on top. A petrol generator carrying 5,000 W burns roughly half a gallon an hour, so a 5 gallon tank gives about 10 hours. Propane needs about 40% more volume for the same energy but stores indefinitely, which is why standby installations favour it. Diesel is the most efficient per gallon and the least tolerant of light loading.
Only through a transfer switch or an interlock kit installed by a qualified electrician. Back-feeding through a dryer outlet — the "suicide cord" — energises the utility lines outside your house and can kill a lineworker. It is also illegal essentially everywhere. A transfer switch also lets you sequence loads, which is exactly what the surge rule assumes.
The load calculation is identical, but inverter generators handle surge less gracefully than conventional ones because there is no rotating mass to draw on — some tolerate very little overload. Check the specific unit's surge rating rather than assuming the usual 20–30% margin. Against that, they idle down under light load, which makes them far more efficient and quieter for small loads.
Last reviewed .
What every household appliance draws, what it costs to run for a year, and where it ranks against everything else in the house.
kVASize a house service the way an electrician does: NEC Article 220 standard calculation, with the demand factors that stop a 40 kW house needing a 400 A service.
FLAFull load current from motor kW or hp, including efficiency — the term most calculators drop, which understates the current by 10–15%.
AWGWhat size wire you need, from the load, the run length and the conditions — sized against both NEC ampacity and voltage drop, with the terminal temperature rule that stops 90 °C wire giving 90 °C ampacity.