6″ offset at 30°
The standard offset. Multiplier of 2 makes the mental arithmetic trivial.
Marks 12″ apart, 1 5/8″ of shrink
Where to put the marks, for any angle rather than the five on the bender — plus the shrink figure that gets forgotten and lands the pipe short of the box.
Inches. How far the conduit has to move sideways.
Degrees. Any angle works — the multiplier is 1/sin θ, not a lookup.
Inches. Where the offset starts.
Multiplier is 2.000, which is simply 1/sin 30°. Marks go 12″ apart — at 12″ and 24″ from the end.
Shrink is 1 5/8″, from tan(15.00°) × 6″. The conduit now travels a diagonal, so the run is that much shorter — add it to your measurement.
The chart on the bender says 2 for 30°; the exact value is 2.0000. On a 6″ offset that is 0″ of difference in mark spacing — negligible here, and worth knowing about on a deep offset.
Choosing the angle is a trade: at 10° the marks are 34 9/16″ apart and the run loses only 1/2″; at 60° they are 6 15/16″ apart but you lose 3 7/16″. Shallow bends pull wire more easily; steep bends fit in less space.
The standard offset. Multiplier of 2 makes the mental arithmetic trivial.
Marks 12″ apart, 1 5/8″ of shrink
Shallow bend for an easier wire pull. Watch the marks move far apart.
Marks 34 9/16″ apart but only 1/2″ of shrink
The usual box offset. Small, and the shrink still matters over a long run.
Marks 7 13/16″ apart
Three-point saddle: 45° centre, 22.5° either side.
Centre mark 30″, outer marks at 20″ and 40″
Take-up is a property of the bender, not the conduit.
Mark at 7″ — 12″ stub less 5″ take-up
When to use this: laying out an offset around an obstruction, saddling over a pipe, or working out where to mark a 90° stub.
Every bender is stamped with the same five numbers — 6 for 10°, 2.6 for 22.5°, 2 for 30°, 1.4 for 45°, 1.2 for 60°. They look like a lookup table to be memorised. They are 1/sin θ, rounded for mental arithmetic.
Knowing that is the difference between bending the five angles the tool is marked for and bending any angle you can measure — which matters when a fixed obstruction dictates the geometry rather than the bender does.
| Angle | Exact multiplier | Chart value | Shrink per inch |
|---|---|---|---|
| 5° | 11.4737 | — | 0.0437 |
| 10° | 5.7588 | 6 | 0.0875 |
| 15° | 3.8637 | — | 0.1317 |
| 22.5° | 2.6131 | 2.6 | 0.1989 |
| 30° | 2.0000 | 2 | 0.2679 |
| 37° | 1.6616 | — | 0.3346 |
| 45° | 1.4142 | 1.4 | 0.4142 |
| 60° | 1.1547 | 1.2 | 0.5774 |
The 37° and 15° rows have no chart value because no bender is marked for them. They work exactly the same way.
Put an offset in a run and the conduit travels a diagonal instead of a straight line, so the far end pulls back toward you. That is shrink, and it is tan(θ/2) per unit of offset depth.
It is small per bend and it accumulates. Three 6″ offsets at 30° in one run lose 4 13/16″ between them — comfortably enough to leave the conduit short of the box after every individual measurement was taken correctly.
| Offset | 10° | 22.5° | 30° | 45° | 60° |
|---|---|---|---|---|---|
| 2″ | 3/16″ | 3/8″ | 9/16″ | 13/16″ | 1 1/8″ |
| 4″ | 3/8″ | 13/16″ | 1 1/16″ | 1 11/16″ | 2 5/16″ |
| 6″ | 1/2″ | 1 3/16″ | 1 5/8″ | 2 1/2″ | 3 7/16″ |
| 10″ | 7/8″ | 2″ | 2 11/16″ | 4 1/8″ | 5 3/4″ |
The traditional pocket chart rounds these down — 3/16″ for 22.5°, 1/4″ for 30°, 3/8″ for 45° — so a run bent to chart figures finishes fractionally short every single time. The exact values are 0.199, 0.268 and 0.414.
| Angle | Marks apart, 6″ offset | Shrink | Suits |
|---|---|---|---|
| 10° | 34 9/16″ | 1/2″ | Long pulls, large conductors |
| 22.5° | 15 11/16″ | 1 3/16″ | General work |
| 30° | 12″ | 1 5/8″ | General work |
| 45° | 8 1/2″ | 2 1/2″ | Tight spaces, short runs |
| 60° | 6 15/16″ | 3 7/16″ | Tight spaces, short runs |
A shallow bend spaces the marks far apart and barely shortens the run, and it is much kinder to a wire pull — every degree of bend multiplies the tension needed. A steep bend fits the offset into a short length and costs you both.
30° is the usual default for one reason: its multiplier is exactly 2, so the arithmetic works in your head on a ladder.
Going over an obstruction rather than around it. A 45° bend at the centre with 22.5° bends either side, in the opposite direction.
Shrink is about 3/16″ per inch of depth. The 2.5 multiplier is specific to this 45°/22.5° combination and is not 1/sin 45° — the geometry involves all three bends, not one.
Take-up is the distance from the end of the conduit to the mark, subtracted from the stub height. It is a property of the bender, not the conduit, and it is stamped on the tool.
| Conduit | Typical take-up | Mark for a 12″ stub | Mark for a 24″ stub |
|---|---|---|---|
| 1″ | 8″ | 4″ | 16″ |
| 2″ | 16″ | too short | 8″ |
| 1/2″ | 5″ | 7″ | 19″ |
| 3/4″ | 6″ | 6″ | 18″ |
| 1-1/4″ | 11″ | 1″ | 13″ |
| 1-1/2″ | 14″ | too short | 10″ |
These are the common published figures. Benders from different manufacturers differ by up to a quarter inch — which is a quarter inch of error on every stub you make, so read your own tool rather than this table.
NEC 344.26 and its equivalents for other raceway types limit a run to 360 degrees total between pull points — four 90° bends, or any combination summing to the same. Note that offsets count: two 30° bends are 60° of the budget.
The limit is about pulling tension, not the conduit. Every bend multiplies the force needed rather than adding to it, so the fourth 90° costs far more than the first. Chapter 9 Table 2 also sets a minimum bend radius by conduit size, which is what stops a tight bend flattening the raceway.
Once the conduit is in, our conduit fill calculator checks the conductors fit it, and box fill handles the boxes at each end.
How far the conduit must move sideways, and how far along the run the move has to happen.
Shallow angles put the marks far apart and pull wire more easily; steep angles fit in less space but shrink the run more. 30° is the usual compromise because its multiplier is exactly 2.
The calculator gives the distance between marks. Bend the first mark, rotate the conduit 180° in the bender, and bend the second in the same direction — the two bends must be in the same plane or the offset will be a dog-leg.
The finished run is shorter than the straight measurement because the conduit now travels a diagonal. Add the shrink figure to your measurement before cutting.
The distance between marks is the offset depth times 1/sin θ. For 30° that is exactly 2, for 45° it is 1.414, for 22.5° it is 2.613, for 10° it is 5.759. The numbers on a bender are these values rounded for mental arithmetic — knowing they are 1/sin θ means you can bend any angle you can measure, not only the five the tool is marked for.
When you put an offset in a run, the conduit travels a diagonal rather than a straight line, so the far end pulls back toward you. The amount is tan(θ/2) per inch of offset — about 1/4 inch per inch at 30°. It is small per bend and it accumulates, and forgetting it is why a pipe with three offsets in it lands short of the box.
Just over a quarter inch per inch of offset — tan(15°) = 0.268. A 6 inch offset at 30° shrinks the run by about 1 5/8 inches. The traditional pocket chart says 1/4 inch per inch, which rounds down; over several bends that rounding is enough to matter.
It is a trade. A shallow angle spaces the marks far apart and barely shrinks the run, and it is much kinder to a wire pull. A steep angle fits the offset into a short length but shrinks more and makes pulling harder. 30° is the common default because its multiplier is exactly 2 and the arithmetic is easy in your head. Use 10° or 22.5° where the pull is long or the conductors are large.
A 45° bend at the centre of the obstruction with 22.5° bends either side. Mark the centre of the obstruction, then mark 2.5 times the saddle depth on each side of it. Bend the centre mark first at 45°, then the two outer marks at 22.5° in the opposite direction. Shrink is about 3/16 inch per inch of depth. The 2.5 multiplier is specific to this 45°/22.5° combination and is not 1/sin 45°.
The distance from the end of the conduit to the mark for a 90° stub of a given height — you subtract it from the stub height. Common published figures are 5 inches for 1/2 inch EMT, 6 for 3/4, 8 for 1 inch, 11 for 1-1/4. It is a property of the bender rather than the conduit and it is stamped on the tool. Benders from different manufacturers differ by a quarter inch, which is a quarter inch of error on every stub if you use the wrong number.
Almost always because the two bends are not in the same plane. After the first bend the conduit must be rotated exactly 180° in the bender before the second, and any error in that rotation shows up as a dog-leg. Sighting down the pipe before the second bend catches it. The other cause is bending from the wrong side of the mark, which changes the offset depth without making it obviously wrong.
NEC 344.26, and the equivalent sections for other raceway types, limit a run to 360 degrees total between pull points. That is four 90° bends, or any combination adding to the same. It is about pulling tension rather than the conduit itself — every bend multiplies the force needed, and the relationship is exponential rather than additive.
No. The offset geometry is trigonometry and applies to any size. What does change with size is the take-up for a 90° stub, because a larger bender has a larger radius, and the practical minimum bend radius allowed by NEC Chapter 9 Table 2.

Technical reviewer
Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region
He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.
The full process is written up in the methodology and editorial policy. Results are engineering guidance, not a code sign-off — see the disclaimer. If a result looks wrong, tell us; corrections are answered before anything else.
How many conductors fit in a conduit, and what size you need. EMT, IMC, RMC and PVC with the real Chapter 9 table areas — including the 31% rule that catches people out.
in³Whether your conductors, devices and clamps fit the box — with the three counting rules that produce nearly every wrong answer: pigtails count zero, all grounds count one, each device counts two.
AWGWhat size wire you need, from the load, the run length and the conditions — sized against both NEC ampacity and voltage drop, with the terminal temperature rule that stops 90 °C wire giving 90 °C ampacity.
kVASize a house service the way an electrician does: NEC Article 220 standard calculation, with the demand factors that stop a 40 kW house needing a 400 A service.