Ground Wire Size Calculator — NEC Table 250.122

Equipment grounding conductor size from the breaker rating — including the 250.122(B) proportional increase almost every other calculator leaves out when a run is upsized for voltage drop.

Inputs

A

The breaker or fuse ahead of the circuit. Not the load, and not the conductor size.

Grounding conductor material
Were the ungrounded conductors upsized?

Usually for voltage drop on a long run. Triggers the 250.122(B) increase.

Each one needs its own full-size EGC — see 250.122(F).

Set this to also get the grounding ELECTRODE conductor from Table 250.66.

Results

Equipment grounding conductor8 AWGTable 250.122, × any 250.122(B) increase
Straight table value
8 AWG
Upsize factor applied
1
Area
1.651e+4
EGCs required
1
Grounding electrode conductor

Table 250.122 gives 8 AWG copper for a 100 A device. The EGC is sized on the overcurrent device — not on the load, and not on the phase conductors.

An EGC carries no current in normal operation. It carries fault current once, for a fraction of a second, and the breaker only trips if the impedance of that path is low enough. That is why the size is not negotiable.

Diagram

Equipment grounding conductor sizeTable 250.122 gives 8 AWG. No upsizing applies.Equipment grounding conductorTable 250.1228 AWG8 AWG · 16,510 cmil

Worked examples

100 A subpanel feeder

The everyday case. Straight table lookup, nothing else applies.

8 AWG copper

30 A circuit — the row that does not exist

Table 250.122 jumps from 20 A to 60 A. People who remember the old table get this wrong.

10 AWG — from the 60 A row, not something between 12 and 10

Upsized for voltage drop — 100 A at 250 ft

The rule other calculators miss. Grow the hots and you must grow the ground with them.

8 AWG becomes 2 AWG — a 3.19× increase in circular mils

Motor circuit — big breaker, small conductors

430.52 allows a 100 A breaker on 12 AWG motor conductors. 250.122(A) caps the ground.

Table says 8 AWG; capped at 12 AWG — never larger than the conductors it grounds

400 A service in three parallel raceways

Each raceway gets a full-size ground. You do not divide it between them.

3 AWG in each of the three raceways, plus a 2 AWG electrode conductor

Reviewed by Salamot Hok, electrician with 10+ years · Last reviewed 17 August 2026

Engineering guidance, not a code sign-off. Verify against the governing standard before relying on this result for safety-critical or code-compliance work.

The ground is sized on the breaker, not on the wire

When to use this: pulling a new circuit, upsizing a feeder for voltage drop, running parallel sets, or checking whether an existing ground is adequate for a breaker that has been changed.

The equipment grounding conductor carries no current in normal operation. It carries fault current once, for a fraction of a second, and the breaker only opens if the impedance of that path is low enough. Nothing appears to be wrong with an undersized ground until the single moment it matters.

Its size comes from Table 250.122, indexed on the rating of the overcurrent device ahead of the circuit. Not the load. Not the conductor size. The common shortcut — “one size smaller than the hots” — is right often enough to feel like a rule and is not one.

Table 250.122

Overcurrent device ratingCopperAluminium
15 A14 AWG12 AWG
20 A12 AWG10 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1,000 A2/0 AWG4/0 AWG
1,200 A3/0 AWG250 kcmil
1,600 A4/0 AWG350 kcmil
2,000 A250 kcmil400 kcmil
2,500 A350 kcmil600 kcmil
3,000 A400 kcmil600 kcmil
4,000 A500 kcmil750 kcmil
5,000 A700 kcmil1200 kcmil
6,000 A800 kcmil1200 kcmil

There is no 30 A row, and that catches people out

The table jumps from 20 A to 60 A. Where your device rating is not listed you take the next row up, so a 30 A or 40 A circuit lands on the 60 A row and needs 10 AWG copper — not something between 12 and 10.

Older editions of the code did have 30 A and 40 A rows. Anyone who learned this table years ago may reach for a smaller conductor than the current code permits, which is a good reason to look it up rather than remember it.

250.122(B): upsize the hots, upsize the ground

This is the rule that separates a correct answer from a plausible one, and the reason this page exists. If the ungrounded conductors are increased in size for any reason, the equipment grounding conductor must be increased proportionally.

It matters because it is not a corner case. Our wire size calculator will tell you to upsize almost any run past about 100 ft — that is what voltage drop does. Every one of those runs also needs a bigger ground, and it is routinely forgotten.

Worked through, for a 100 A circuit upsized from 3 AWG to 3/0 for a long run:

StepValue
Conductor required by ampacity3 AWG — 52,620 cmil
Conductor actually installed3/0 AWG — 167,800 cmil
Upsize ratio3.1889×
EGC from Table 250.1228 AWG16,510 cmil
Minimum EGC area after 250.122(B)52,649 cmil
EGC required2 AWG 66,360 cmil

Note how close that lands. The requirement is 52,649 cmil and 3 AWG is 52,620 — short by 29 circular mils. So the answer is 2 AWG, not 3 AWG. Rounding the ratio, or estimating “about three sizes up”, gets this wrong.

Do the increase by circular mils, not by counting AWG steps. Each AWG step is roughly a 1.26× change in area, so “go up two sizes” means 1.6× — which is sometimes generous and sometimes short, depending where on the ladder you started.

The cap that stops it running away

250.122(A) also says the EGC is never required to be larger than the circuit conductors it grounds. This matters most on motor circuits, where 430.52 permits a breaker sized for locked-rotor inrush far above what the conductors would otherwise take: a 100 A breaker ahead of 12 AWG motor conductors would call for 8 AWG from the table, and the cap brings it back to 12 AWG.

There is a quieter property worth knowing: on an ordinary voltage-drop upsize the cap never fires. Scaling the ground by the same ratio as the phase conductors cannot overshoot them.

Parallel runs: one full-size ground per raceway

250.122(F) requires a full-size equipment grounding conductor in every raceway of a parallel set, each sized on the single overcurrent device protecting the whole set. Three parallel runs on a 400 A breaker need three 3 AWG grounds — not one, and not a third of one each.

The reason is simply that a fault can occur in any of the raceways, and the ground in that raceway has to clear it alone. Dividing the ground between runs would leave each one unable to do the job on its own.

EGC or GEC? They are not the same conductor

This is the most common misunderstanding in Article 250, and the two are sized from different tables on different inputs.

Equipment grounding conductorGrounding electrode conductor
Table250.122250.66
Sized onOvercurrent device ratingService-entrance conductor size
JobCarry fault current back to the source so a breaker tripsConnect the system to earth
Where it runsWith every circuitService equipment to the electrode
Upper limitGrows with the device, to 800 kcmilStops at 3/0 copper, however large the service

The GEC stops growing because earth is not a fault-current path. Soil resistance is measured in ohms, so a ground rod passes a few amps at best — nowhere near enough to open a breaker. Earth stabilises voltage to ground and gives lightning somewhere to go. The conductor that actually clears faults is the EGC, running back to the source.

People who believe otherwise sometimes drive a rod at an outbuilding and omit the equipment ground, which leaves a fault with no low-impedance path at all and a breaker that will not trip.

Table 250.66 — grounding electrode conductor

Largest ungrounded service conductor (copper)Copper GECAluminium GEC
2 AWG or smaller8 AWG6 AWG
1 or 1/06 AWG4 AWG
2/0 or 3/04 AWG2 AWG
Over 3/0 to 350 kcmil2 AWG1/0 AWG
Over 350 to 600 kcmil1/0 AWG3/0 AWG
Over 600 to 1100 kcmil2/0 AWG4/0 AWG
Over 1100 kcmil3/0 AWG250 kcmil

The aluminium column of the table is indexed on aluminium service conductors, whose thresholds are larger than the copper ones — an aluminium service reads a different row than a copper service of the same circular-mil area. The calculator handles this; reading the table casually does not.

One exception worth remembering: 250.66(A) caps the conductor to a ground rod at 6 AWG, and 250.66(B) caps the conductor to a concrete-encased electrode at 4 AWG, whatever the table says. A bigger conductor into soil achieves nothing.

Details that change the answer

  • Green is reserved. 250.119 allows green, green with yellow stripes, or bare for equipment grounding conductors and nothing else. IEC practice differs — plain green is not used there — so imported equipment may carry colours that mean something else.
  • Conduit can be the ground. 250.118 lists RMC, IMC and EMT among permitted types. Many designers pull a wire anyway, because raceway continuity depends on every coupling staying tight for decades and cannot be inspected behind a wall.
  • Aluminium has placement rules. 250.120(B) prohibits it in direct contact with masonry or earth, in a wet location within a raceway, and within 450 mm (18 in) of earth.
  • The neutral is not a ground. Bonding them anywhere downstream of the service disconnect puts normal load current on metal enclosures. Subpanels get separated bars.
  • Flexible metal conduit has limits. FMC and LFMC qualify as an EGC only in short lengths with appropriately sized overcurrent protection — 250.118(5) and (6). Beyond those, pull a wire.

Once the ground is sized, check the whole bundle fits: our conduit fill calculator counts the EGC like any other conductor, and the wire size calculator is where the upsizing that triggers 250.122(B) usually comes from.

How to use this calculator

  1. Find the overcurrent device rating

    The breaker or fuse protecting the circuit, ahead of the raceway. This is the only input the table uses — not the load, not the conductor size.

  2. Read the next row up

    If your rating is not a row in the table, take the next larger one. A 30 A or 40 A circuit uses the 60 A row.

  3. Say whether the conductors were upsized

    If you increased the phase conductors for voltage drop or any other reason, 250.122(B) requires the same proportional increase in the ground, by circular-mil area.

  4. Count the raceways

    Conductors run in parallel need a full-size equipment grounding conductor in every raceway, each sized on the single overcurrent device.

  5. Check it against the phase conductors

    The EGC is never required to be larger than the circuit conductors it grounds. On motor circuits, where the breaker is sized for inrush, this cap frequently applies.

Frequently asked questions

What size ground wire do I need?

It depends on the breaker, not the load. For a 15 A circuit, 14 AWG copper; 20 A, 12 AWG; 30 A through 60 A, 10 AWG; 100 A, 8 AWG; 200 A, 6 AWG. Aluminium is one to two sizes larger throughout. If the phase conductors were upsized for voltage drop, all of these increase proportionally.

Why is there no 30 amp row in Table 250.122?

Modern editions of the NEC jump from 20 A straight to 60 A. Where your device rating is not listed you use the next row up, so a 30 A or 40 A circuit takes the 60 A row and needs 10 AWG copper. Older editions did have 30 A and 40 A rows, which is why people who learned the table years ago sometimes reach for a smaller conductor than the current code allows.

Do I have to upsize the ground if I upsize the wire for voltage drop?

Yes — NEC 250.122(B) requires it, and it is the most commonly missed rule in this area. The increase is proportional by circular-mil area, not by AWG steps. If you went from 3 AWG to 3/0 for a long run, that is a 3.19× increase in area, so an 8 AWG ground becomes 2 AWG. Skipping this leaves the fault-current path with more impedance than the overcurrent device was selected for, which is exactly the condition that stops a breaker clearing a ground fault quickly.

Can the ground wire be smaller than the hot wires?

Usually yes, and that is normal. A 100 A feeder in 3 AWG copper takes an 8 AWG ground. The EGC only has to carry fault current long enough for the breaker to open, not continuous load current. What it must not be is smaller than Table 250.122 requires — and it is never required to be larger than the circuit conductors themselves.

What is the difference between an EGC and a grounding electrode conductor?

They do different jobs and are sized from different tables. The equipment grounding conductor (Table 250.122) bonds metal equipment back to the source so fault current can trip a breaker — it is sized on the overcurrent device. The grounding electrode conductor (Table 250.66) connects the system to earth, is sized on the service-entrance conductors, and tops out at 3/0 copper however large the service. Earth is not a fault-current path; it stabilises voltage and handles lightning. Confusing the two is the most common misunderstanding in NEC Article 250.

Do parallel conductors need a ground in every conduit?

Yes. NEC 250.122(F) requires a full-size equipment grounding conductor in each raceway, and each one is sized on the single overcurrent device protecting the whole set — not on a share of it. Three parallel runs on a 400 A breaker need three 3 AWG grounds, not one. Each raceway must be able to carry fault current on its own, because a fault can occur in any of them.

Does conduit count as the equipment grounding conductor?

It can. NEC 250.118 lists rigid metal conduit, intermediate metal conduit and electrical metallic tubing among the permitted types, subject to conditions on fittings and length. Many designers still pull a wire-type EGC because raceway continuity depends on every coupling staying tight for decades, and because a wire ground is inspectable in a way that a threaded joint behind a wall is not.

Can I use aluminium for a ground wire?

Yes, sized from the aluminium column, but 250.120(B) prohibits it in several places: in direct contact with masonry or earth, in a wet location inside a raceway, and within 450 mm (18 in) of earth. Terminations must be listed for aluminium. Given the sizes involved on branch circuits are small, copper is usually the simpler choice below feeder scale.

What size ground for a 200 amp service?

Two different conductors, and this is where the confusion above becomes expensive. The equipment grounding conductor for a 200 A device is 6 AWG copper from Table 250.122. The grounding electrode conductor for a 200 A service with 4/0 aluminium or 2/0 copper conductors is 4 AWG copper from Table 250.66. If the electrode is a ground rod, 250.66(A) caps the conductor to it at 6 AWG regardless.

Is a green wire always the ground?

In North American practice yes — 250.119 reserves green, green with yellow stripes, and bare for equipment grounding conductors, and nothing else may use them. Note that this is a different convention from IEC practice, where green-and-yellow is protective earth and plain green is not used, so imported equipment can carry colours that mean something else.

Sources and further reading

How this calculator is checked

Salamot Hok, Technical reviewer

Technical reviewer

Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region

He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.

  • The maths lives in a pure function with its own test suite, asserted against worked examples from published references and standards. A calculator does not ship until those tests pass.
  • 3 sources cited by name and linked, so any figure on the page can be traced back to the document it came from.
  • Last reviewed . Review dates are advanced only when the page is actually re-read, never to look fresh.
  • Unusable input returns no answer. Where the inputs do not describe a real design, the calculator says so and withholds the number rather than printing a plausible-looking wrong one.

Related calculators