100 A subpanel feeder
The everyday case. Straight table lookup, nothing else applies.
8 AWG copper
Equipment grounding conductor size from the breaker rating — including the 250.122(B) proportional increase almost every other calculator leaves out when a run is upsized for voltage drop.
The breaker or fuse ahead of the circuit. Not the load, and not the conductor size.
Usually for voltage drop on a long run. Triggers the 250.122(B) increase.
Each one needs its own full-size EGC — see 250.122(F).
Set this to also get the grounding ELECTRODE conductor from Table 250.66.
Table 250.122 gives 8 AWG copper for a 100 A device. The EGC is sized on the overcurrent device — not on the load, and not on the phase conductors.
An EGC carries no current in normal operation. It carries fault current once, for a fraction of a second, and the breaker only trips if the impedance of that path is low enough. That is why the size is not negotiable.
The everyday case. Straight table lookup, nothing else applies.
8 AWG copper
Table 250.122 jumps from 20 A to 60 A. People who remember the old table get this wrong.
10 AWG — from the 60 A row, not something between 12 and 10
The rule other calculators miss. Grow the hots and you must grow the ground with them.
8 AWG becomes 2 AWG — a 3.19× increase in circular mils
430.52 allows a 100 A breaker on 12 AWG motor conductors. 250.122(A) caps the ground.
Table says 8 AWG; capped at 12 AWG — never larger than the conductors it grounds
Each raceway gets a full-size ground. You do not divide it between them.
3 AWG in each of the three raceways, plus a 2 AWG electrode conductor
When to use this: pulling a new circuit, upsizing a feeder for voltage drop, running parallel sets, or checking whether an existing ground is adequate for a breaker that has been changed.
The equipment grounding conductor carries no current in normal operation. It carries fault current once, for a fraction of a second, and the breaker only opens if the impedance of that path is low enough. Nothing appears to be wrong with an undersized ground until the single moment it matters.
Its size comes from Table 250.122, indexed on the rating of the overcurrent device ahead of the circuit. Not the load. Not the conductor size. The common shortcut — “one size smaller than the hots” — is right often enough to feel like a rule and is not one.
| Overcurrent device rating | Copper | Aluminium |
|---|---|---|
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 60 A | 10 AWG | 8 AWG |
| 100 A | 8 AWG | 6 AWG |
| 200 A | 6 AWG | 4 AWG |
| 300 A | 4 AWG | 2 AWG |
| 400 A | 3 AWG | 1 AWG |
| 500 A | 2 AWG | 1/0 AWG |
| 600 A | 1 AWG | 2/0 AWG |
| 800 A | 1/0 AWG | 3/0 AWG |
| 1,000 A | 2/0 AWG | 4/0 AWG |
| 1,200 A | 3/0 AWG | 250 kcmil |
| 1,600 A | 4/0 AWG | 350 kcmil |
| 2,000 A | 250 kcmil | 400 kcmil |
| 2,500 A | 350 kcmil | 600 kcmil |
| 3,000 A | 400 kcmil | 600 kcmil |
| 4,000 A | 500 kcmil | 750 kcmil |
| 5,000 A | 700 kcmil | 1200 kcmil |
| 6,000 A | 800 kcmil | 1200 kcmil |
The table jumps from 20 A to 60 A. Where your device rating is not listed you take the next row up, so a 30 A or 40 A circuit lands on the 60 A row and needs 10 AWG copper — not something between 12 and 10.
Older editions of the code did have 30 A and 40 A rows. Anyone who learned this table years ago may reach for a smaller conductor than the current code permits, which is a good reason to look it up rather than remember it.
This is the rule that separates a correct answer from a plausible one, and the reason this page exists. If the ungrounded conductors are increased in size for any reason, the equipment grounding conductor must be increased proportionally.
It matters because it is not a corner case. Our wire size calculator will tell you to upsize almost any run past about 100 ft — that is what voltage drop does. Every one of those runs also needs a bigger ground, and it is routinely forgotten.
Worked through, for a 100 A circuit upsized from 3 AWG to 3/0 for a long run:
| Step | Value |
|---|---|
| Conductor required by ampacity | 3 AWG — 52,620 cmil |
| Conductor actually installed | 3/0 AWG — 167,800 cmil |
| Upsize ratio | 3.1889× |
| EGC from Table 250.122 | 8 AWG — 16,510 cmil |
| Minimum EGC area after 250.122(B) | 52,649 cmil |
| EGC required | 2 AWG — 66,360 cmil |
Note how close that lands. The requirement is 52,649 cmil and 3 AWG is 52,620 — short by 29 circular mils. So the answer is 2 AWG, not 3 AWG. Rounding the ratio, or estimating “about three sizes up”, gets this wrong.
Do the increase by circular mils, not by counting AWG steps. Each AWG step is roughly a 1.26× change in area, so “go up two sizes” means 1.6× — which is sometimes generous and sometimes short, depending where on the ladder you started.
250.122(A) also says the EGC is never required to be larger than the circuit conductors it grounds. This matters most on motor circuits, where 430.52 permits a breaker sized for locked-rotor inrush far above what the conductors would otherwise take: a 100 A breaker ahead of 12 AWG motor conductors would call for 8 AWG from the table, and the cap brings it back to 12 AWG.
There is a quieter property worth knowing: on an ordinary voltage-drop upsize the cap never fires. Scaling the ground by the same ratio as the phase conductors cannot overshoot them.
250.122(F) requires a full-size equipment grounding conductor in every raceway of a parallel set, each sized on the single overcurrent device protecting the whole set. Three parallel runs on a 400 A breaker need three 3 AWG grounds — not one, and not a third of one each.
The reason is simply that a fault can occur in any of the raceways, and the ground in that raceway has to clear it alone. Dividing the ground between runs would leave each one unable to do the job on its own.
This is the most common misunderstanding in Article 250, and the two are sized from different tables on different inputs.
| Equipment grounding conductor | Grounding electrode conductor | |
|---|---|---|
| Table | 250.122 | 250.66 |
| Sized on | Overcurrent device rating | Service-entrance conductor size |
| Job | Carry fault current back to the source so a breaker trips | Connect the system to earth |
| Where it runs | With every circuit | Service equipment to the electrode |
| Upper limit | Grows with the device, to 800 kcmil | Stops at 3/0 copper, however large the service |
The GEC stops growing because earth is not a fault-current path. Soil resistance is measured in ohms, so a ground rod passes a few amps at best — nowhere near enough to open a breaker. Earth stabilises voltage to ground and gives lightning somewhere to go. The conductor that actually clears faults is the EGC, running back to the source.
People who believe otherwise sometimes drive a rod at an outbuilding and omit the equipment ground, which leaves a fault with no low-impedance path at all and a breaker that will not trip.
| Largest ungrounded service conductor (copper) | Copper GEC | Aluminium GEC |
|---|---|---|
| 2 AWG or smaller | 8 AWG | 6 AWG |
| 1 or 1/0 | 6 AWG | 4 AWG |
| 2/0 or 3/0 | 4 AWG | 2 AWG |
| Over 3/0 to 350 kcmil | 2 AWG | 1/0 AWG |
| Over 350 to 600 kcmil | 1/0 AWG | 3/0 AWG |
| Over 600 to 1100 kcmil | 2/0 AWG | 4/0 AWG |
| Over 1100 kcmil | 3/0 AWG | 250 kcmil |
The aluminium column of the table is indexed on aluminium service conductors, whose thresholds are larger than the copper ones — an aluminium service reads a different row than a copper service of the same circular-mil area. The calculator handles this; reading the table casually does not.
One exception worth remembering: 250.66(A) caps the conductor to a ground rod at 6 AWG, and 250.66(B) caps the conductor to a concrete-encased electrode at 4 AWG, whatever the table says. A bigger conductor into soil achieves nothing.
Once the ground is sized, check the whole bundle fits: our conduit fill calculator counts the EGC like any other conductor, and the wire size calculator is where the upsizing that triggers 250.122(B) usually comes from.
The breaker or fuse protecting the circuit, ahead of the raceway. This is the only input the table uses — not the load, not the conductor size.
If your rating is not a row in the table, take the next larger one. A 30 A or 40 A circuit uses the 60 A row.
If you increased the phase conductors for voltage drop or any other reason, 250.122(B) requires the same proportional increase in the ground, by circular-mil area.
Conductors run in parallel need a full-size equipment grounding conductor in every raceway, each sized on the single overcurrent device.
The EGC is never required to be larger than the circuit conductors it grounds. On motor circuits, where the breaker is sized for inrush, this cap frequently applies.
It depends on the breaker, not the load. For a 15 A circuit, 14 AWG copper; 20 A, 12 AWG; 30 A through 60 A, 10 AWG; 100 A, 8 AWG; 200 A, 6 AWG. Aluminium is one to two sizes larger throughout. If the phase conductors were upsized for voltage drop, all of these increase proportionally.
Modern editions of the NEC jump from 20 A straight to 60 A. Where your device rating is not listed you use the next row up, so a 30 A or 40 A circuit takes the 60 A row and needs 10 AWG copper. Older editions did have 30 A and 40 A rows, which is why people who learned the table years ago sometimes reach for a smaller conductor than the current code allows.
Yes — NEC 250.122(B) requires it, and it is the most commonly missed rule in this area. The increase is proportional by circular-mil area, not by AWG steps. If you went from 3 AWG to 3/0 for a long run, that is a 3.19× increase in area, so an 8 AWG ground becomes 2 AWG. Skipping this leaves the fault-current path with more impedance than the overcurrent device was selected for, which is exactly the condition that stops a breaker clearing a ground fault quickly.
Usually yes, and that is normal. A 100 A feeder in 3 AWG copper takes an 8 AWG ground. The EGC only has to carry fault current long enough for the breaker to open, not continuous load current. What it must not be is smaller than Table 250.122 requires — and it is never required to be larger than the circuit conductors themselves.
They do different jobs and are sized from different tables. The equipment grounding conductor (Table 250.122) bonds metal equipment back to the source so fault current can trip a breaker — it is sized on the overcurrent device. The grounding electrode conductor (Table 250.66) connects the system to earth, is sized on the service-entrance conductors, and tops out at 3/0 copper however large the service. Earth is not a fault-current path; it stabilises voltage and handles lightning. Confusing the two is the most common misunderstanding in NEC Article 250.
Yes. NEC 250.122(F) requires a full-size equipment grounding conductor in each raceway, and each one is sized on the single overcurrent device protecting the whole set — not on a share of it. Three parallel runs on a 400 A breaker need three 3 AWG grounds, not one. Each raceway must be able to carry fault current on its own, because a fault can occur in any of them.
It can. NEC 250.118 lists rigid metal conduit, intermediate metal conduit and electrical metallic tubing among the permitted types, subject to conditions on fittings and length. Many designers still pull a wire-type EGC because raceway continuity depends on every coupling staying tight for decades, and because a wire ground is inspectable in a way that a threaded joint behind a wall is not.
Yes, sized from the aluminium column, but 250.120(B) prohibits it in several places: in direct contact with masonry or earth, in a wet location inside a raceway, and within 450 mm (18 in) of earth. Terminations must be listed for aluminium. Given the sizes involved on branch circuits are small, copper is usually the simpler choice below feeder scale.
Two different conductors, and this is where the confusion above becomes expensive. The equipment grounding conductor for a 200 A device is 6 AWG copper from Table 250.122. The grounding electrode conductor for a 200 A service with 4/0 aluminium or 2/0 copper conductors is 4 AWG copper from Table 250.66. If the electrode is a ground rod, 250.66(A) caps the conductor to it at 6 AWG regardless.
In North American practice yes — 250.119 reserves green, green with yellow stripes, and bare for equipment grounding conductors, and nothing else may use them. Note that this is a different convention from IEC practice, where green-and-yellow is protective earth and plain green is not used, so imported equipment can carry colours that mean something else.

Technical reviewer
Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region
He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.
The full process is written up in the methodology and editorial policy. Results are engineering guidance, not a code sign-off — see the disclaimer. If a result looks wrong, tell us; corrections are answered before anything else.
Minimum conductor size to survive a fault, S = √(I²t) ÷ k, to BS 7671 Regulation 543.1.3 — with k derived from the conductor material and its permitted temperature rise rather than looked up.
ZsZs = Ze + (R1 + R2) against the maximum permitted for the protective device, to BS 7671 Chapter 41 — with the maximum derived from U0 × Cmin ÷ Ia rather than looked up, and the cold-measurement rule applied separately.
AWGWhat size wire you need, from the load, the run length and the conditions — sized against both NEC ampacity and voltage drop, with the terminal temperature rule that stops 90 °C wire giving 90 °C ampacity.
IpfThe highest current a fault could produce, from a loop impedance, a transformer nameplate or your meter readings — checked against the breaking capacity of the device that has to interrupt it.