7.5 kW three-phase, 400 V
A standard industrial motor — pump, fan or conveyor drive.
14.15 A FLA, size conductors for 17.7 A, 85 A starting surge
Full load current from motor kW or hp, including efficiency — the term most calculators drop, which understates the current by 10–15%.
The nameplate figure — mechanical power at the shaft, not electrical input.
IE3 motors are 89–94% depending on size. From the nameplate where possible.
1.15 is common on North American motors; 1.0 elsewhere.
Size branch-circuit conductors for 17.7 A — NEC 430.22 requires 125% of full load current for a continuous-duty motor.
Direct-on-line starting draws roughly 84.9 A (6× FLA). Protection must tolerate this inrush without tripping, which is why motor circuits use time-delay devices rather than ordinary breakers.
0.833 kW is lost as heat inside the motor. That is what the cooling fan has to remove, and what an enclosure has to dissipate.
For NEC conductor and overload sizing in the United States, use the table values in NEC 430.248–430.250 rather than this calculated figure or the nameplate. The tables are what the code requires; the nameplate is only used for overload protection.
A standard industrial motor — pump, fan or conveyor drive.
14.15 A FLA, size conductors for 17.7 A, 85 A starting surge
The same job in imperial units on a US industrial supply.
11.9 A FLA — but always check NEC Table 430.250 for the code figure
A workshop machine on a domestic supply. Note the current compared to three-phase.
14.1 A — near the limit of a 16 A circuit before inrush is considered
A drive removes the inrush problem entirely, which often lets you use smaller protection.
Starting current drops from 85 A to 21 A
When to use this: sizing cable and protection for a motor circuit, checking whether an existing supply can take another machine, or verifying that a motor is drawing what it should rather than something worrying.
Full load current is the motor's rated output divided by everything it takes to get there:
Three-phase: I = P_out / (√3 × V × η × cos φ)Single-phase: I = P_out / (V × η × cos φ)
P_out is the nameplate rating — mechanical power at the shaft. η is efficiency and cos φ is power factor, both also on the nameplate.
This is the most common mistake in the calculation. The nameplate says 7.5 kW, but that is what the motor delivers at the shaft. To deliver it, the motor must draw more, because some is lost as heat in the windings, iron and bearings.
Electrical input = 7.5 kW / 0.90 = 8.33 kW
Leaving efficiency out understates the current by 10–15%. On a circuit sized close to its limit, that is the difference between a cable that runs warm and one that runs hot.
If you are working under the National Electrical Code in the United States, do not size conductors from this calculation or from the nameplate.
NEC 430.6(A)(1) requires branch-circuit conductor and short-circuit protection sizing to use the current values in Tables 430.248 through 430.250 — tables of typical currents by horsepower and voltage. The nameplate current is used only for overload protection sizing under 430.32.
The table values are deliberately generic and often differ from a specific motor's actual nameplate. That is intentional: it means a replacement motor of the same horsepower will always fit the existing circuit. This calculator gives you the engineering figure, which is the right number outside NEC jurisdictions and for sanity-checking — but the code number is what an inspector will check.
An induction motor at standstill looks electrically like a short-circuited transformer. Until it turns, there is no back-EMF opposing the supply, so it draws enormous current — typically six times full load, for a few seconds.
| Starting method | Inrush | Starting torque | Suits |
|---|---|---|---|
| Direct-on-line | ~6× FLA | 100% | Small motors, stiff supplies |
| Star-delta | ~2× FLA | 33% | Fans, centrifugal pumps — loads that start unloaded |
| Soft starter | ~3× FLA | Adjustable | Conveyors, anything where mechanical shock matters |
| VFD | ~1.5× FLA | Full, from zero speed | Anything, if you also want speed control |
Protection has to ride through this surge. That is why motor circuits use time-delay fuses, motor-rated circuit breakers or motor protection relays rather than ordinary breakers — an ordinary breaker sized for the running current would trip on every start.
Input = 7500 / 0.90 = 8333 WI = 8333 / (1.732 × 400 × 0.85) = 14.15 AConductors at 125% = 17.7 ADOL starting ≈ 85 A for a few seconds
A 2.5 mm² cable handles 17.7 A comfortably. The protection needs to be motor-rated to tolerate the 85 A surge — a standard 20 A breaker would trip instantly on start.
Input = 2200 / 0.85 = 2588 WI = 2588 / (230 × 0.80) = 14.1 A
Almost the same current as the 7.5 kW three-phase motor, for less than a third of the mechanical output. That is the case for three-phase in one line: for the same power, the current is √3 times lower, so conductors, contactors and switchgear are all smaller.
The magnetising current that establishes the rotating field is roughly constant regardless of load. The working current scales with load. At light load the magnetising component dominates, so power factor collapses:
| Load | Typical efficiency | Typical power factor |
|---|---|---|
| 100% | 90% | 0.85 |
| 75% | 89% | 0.81 |
| 50% | 86% | 0.71 |
| 25% | 75% | 0.47 |
A motor at 25% load draws current at 0.47 power factor — the supply carries roughly double the current per useful watt compared to full load. Specifying a motor "with margin" costs money continuously, not once.
In kW or hp. This is shaft output — the mechanical power the motor delivers, not what it draws.
Both are on the nameplate. Efficiency is what converts shaft output into electrical input, and dropping it is the most common error in this calculation.
Direct-on-line draws about six times FLA for a few seconds. That surge, not the running current, is what protection has to tolerate.
NEC 430.22 requires branch-circuit conductors rated for 125% of full load current on a continuous-duty motor.
For three-phase: I = P_output / (√3 × V × efficiency × power factor). For single-phase, drop the √3. A 7.5 kW motor at 400 V, 90% efficient with 0.85 power factor draws 7500 / (1.732 × 400 × 0.9 × 0.85) = 14.15 A.
The nameplate kW is mechanical power at the shaft, but current is drawn to supply electrical input, which is larger by the efficiency. A 90% efficient 7.5 kW motor draws 8.33 kW electrically. Leaving efficiency out understates the current by 10–15%, which is enough to undersize a cable.
Neither, for code compliance in the United States. NEC 430.6(A)(1) requires conductor and short-circuit protection sizing to use the table values in 430.248–430.250, not the nameplate and not a calculated figure. The nameplate current is used only for overload protection sizing. This calculator is for engineering estimates and non-NEC jurisdictions.
An induction motor started direct-on-line draws roughly six times its full load current for a few seconds until it reaches speed. Protection must ride through that surge without tripping, which is why motor circuits use time-delay fuses or motor-rated breakers rather than ordinary ones.
To about a third — roughly 2× FLA instead of 6×. The trade-off is that starting torque falls by the same factor, so it only suits loads that start unloaded, such as fans and centrifugal pumps. A conveyor or compressor may not accelerate at all.
A multiplier showing how far above nameplate rating the motor can run continuously without damage. A 1.15 service factor on a 10 hp motor means it will tolerate 11.5 hp. It is headroom for occasional overload, not a licence to run there permanently — sustained operation in the service factor range shortens insulation life.
The magnetising current that establishes the rotating field is roughly constant regardless of load, while the working current scales with load. At light load the magnetising component dominates, so power factor collapses — often to 0.4 or lower. This is the main argument against oversizing motors.
One mechanical horsepower is 745.7 W, so multiply hp by 0.7457 to get kW. A 10 hp motor is 7.46 kW. Note that motors are rated in output power in both systems, so the conversion applies to the shaft rating directly.
Last reviewed .
kW, kVA and kVAr from line voltage and current, with star and delta phase values and what power factor correction would save you.
ΔVVoltage drop for DC, single-phase and three-phase runs in copper or aluminium, sized in mm² or AWG, checked against IEC and NEC limits.
AWGDiameter, cross-section, resistance and current rating for any AWG size — with separate free-air and in-conduit ampacity, because they differ by a factor of two.
WPower from any two of voltage, current and resistance — then energy in kWh and what it costs to run.