Adding a dryer to a 100 A panel
A comfortable case — room on both counts.
4.2 A spare, 4 spaces left
Whether your existing panel has room for a new circuit — in amps and in breaker spaces, which are different constraints and only one of them is visible through the door.
The number on the main breaker, not the number of spaces.
240 V for a residential service, 208 V for a three-phase commercial panel.
VA, from a load calculation — not from adding up the breakers.
Check the label. Physically fitting is not the same as being approved.
VA. An EV charger at 40 A 240 V is 9,600 VA.
1 for a 120 V circuit, 2 for a 240 V one.
Counted at 125%. EV charging and electric heat qualify.
It fits, on both counts: 15.0 A of capacity spare and 4 spaces left after this circuit.
Capacity is the binding constraint here, not spaces — 15% of the amps are spare against 20% of the spaces. That is the usual situation and the one people miss, because empty spaces are visible through the panel door and the calculated load is not.
The panel is at 85% of rating. Nothing prohibits that, but it leaves very little for the next appliance — and heat pumps, EV chargers and induction ranges are exactly the loads people add to older panels.
A comfortable case — room on both counts.
4.2 A spare, 4 spaces left
A 48 A charger is continuous, so it counts at 125%. This is where it breaks.
Over capacity — spaces are free but the amps are not
The fixable case. Tandems or a small subpanel solve it.
Capacity to spare, one space free, needs two
What an upgraded service buys you.
Comfortable on both constraints
When to use this: adding a circuit to a panel that already exists — an EV charger, a hot tub, a heat pump — and wanting to know before you buy the breaker.
“Is there room in the panel?” is two separate questions that people merge into one:
A panel can be full of empty spaces and out of capacity, or out of spaces with capacity to spare. Those need completely different fixes, and one of them costs twenty times the other.
| Problem | Fix | Rough cost |
|---|---|---|
| Out of spaces, capacity to spare | Tandem breaker, or a small subpanel | Low |
| Out of capacity | Load management, or a service upgrade | High |
| Out of both | Service upgrade with a larger panel | High |
A subpanel adds spaces, not capacity — it is fed from the existing service and shares it. If the constraint is amps, a subpanel changes nothing whatsoever. That distinction is worth being clear about before anyone quotes for one.
The most common way people estimate panel load is to total the breaker ratings, and it overstates the answer enormously. A typical house has 200 A or more of breakers on a 100 A service and is entirely compliant.
Circuits are sized for their worst case, and NEC Article 220 applies demand factors because they never all run at once — 3,000 VA of lighting at 100% and the rest at 35%, ranges from Table 220.55, the larger of heating or cooling but never both. Our load calculator does that arithmetic; this page starts from its answer.
VA for common additions. The continuous ones count at 125% under 210.19(A)(1), which is the same rule as “a breaker may carry only 80% continuously” stated from the other end.
| Load | VA | Continuous? | Counts as |
|---|---|---|---|
| LED lighting circuit | 600 | No | 600 |
| General receptacle circuit | 1,800 | No | 1,800 |
| Dishwasher | 1,500 | No | 1,500 |
| Microwave | 1,500 | No | 1,500 |
| Electric dryer | 5,000 | No | 5,000 |
| Electric range | 12,000 | No | 12,000 |
| Electric water heater | 4,500 | Yes | 5,625 |
| Air conditioner, 3 ton | 3,500 | No | 3,500 |
| Heat pump, 3 ton | 7,000 | Yes | 8,750 |
| EV charger, 32 A | 7,680 | Yes | 9,600 |
| EV charger, 48 A | 11,520 | Yes | 14,400 |
| Hot tub | 7,500 | Yes | 9,375 |
The EV charger rows are where 100 A services break. A 48 A charger is 11,520 VA on paper and 14,400 VA in the calculation — around 60 A of a 100 A service before anything else is switched on.
A tandem fits two circuits into one full-size position. They are permitted only where the panel is listed for them, and only in the positions the label identifies — often just the bottom few.
NEC 408.36 limits a panelboard to the number of overcurrent devices it is marked for. A panel rated for 20 devices does not become a 40-device panel because tandems physically fit in the slots, and inspectors check this.
Note also that a tandem gives you two 120 V circuits, not a 240 V one. A hot tub or EV charger needs two adjacent full-size positions on opposite busbars, which a tandem cannot provide.
Where the constraint is amps and a service upgrade is not practical, NEC 625.42 recognises load management for EV charging: a device that monitors the service and pauses or reduces charging when the house draws heavily. The circuit is then sized on the managed maximum rather than the charger's rating.
It is increasingly the answer for older housing stock, and it is considerably cheaper than moving a service. The same principle appears in 220.70 for energy management systems more generally.
Nothing prohibits running a panel to 100% of its calculated capacity. It is not good practice. Above roughly 80% it is worth asking what is coming in the next few years — because heat pumps, induction ranges and EV chargers are precisely the loads people add to older panels, and each one arrives as a surprise.
If you are considering an upgrade anyway, sizing for one circuit and then upgrading again in two years is the expensive path. Our load calculator will size the service properly, and wire size handles the feeder to any new subpanel.
The number on the main breaker. This is the panel’s capacity in amps, and it is not related to how many breaker spaces it has.
From a load calculation, not by adding up the breaker ratings. Adding breakers overstates the load enormously, because circuits are sized for the worst case and never all run at once.
Total positions and how many are occupied. A two-pole breaker uses two.
Its VA, how many poles, and whether it is continuous. EV charging and electric heat are continuous and count at 125%.
Amps and spaces are separate. Running out of spaces is cheap to fix; running out of capacity is not.
Two separate questions. Does it have a free breaker space, and does it have spare capacity in amps? A panel can be full of empty spaces and out of capacity, or out of spaces with plenty of capacity. The first needs load management or a service upgrade; the second is solved with a tandem breaker or a subpanel for a fraction of the cost.
From a load calculation under NEC Article 220, not by adding up the breaker ratings. A typical house has 200 A or more of breakers on a 100 A service and is perfectly compliant, because circuits are sized for their worst case and demand factors recognise that they never all run at once. Our load calculator does the Article 220 arithmetic.
A breaker that fits two circuits into one full-size space. They are permitted only where the panel is listed for them, and only in the specific positions the label identifies — often just the bottom few. NEC 408.36 limits a panelboard to the number of overcurrent devices it is marked for, so a panel rated for 20 devices does not become a 40-device panel because tandems physically fit.
Because it is a continuous load, so it counts at 125% of its rating. A 48 A charger is 11,520 VA on paper and 14,400 VA in the calculation — around 60 A of a 100 A service before anything else is switched on. Load management devices that pause charging when the house draws heavily are increasingly the answer, and the code recognises them under 625.42.
The same rule as the 125% continuous load factor, stated from the other end. A breaker may carry a continuous load of no more than 80% of its rating, which is arithmetically identical to sizing the circuit at 125% of the load. A 20 A breaker takes a 16 A continuous load.
A subpanel adds spaces, not capacity — it is fed from the existing service and shares it. If you are out of spaces with capacity to spare, a subpanel is the cheap and correct answer. If you are out of capacity, a subpanel changes nothing at all and a service upgrade is the only real option.
Nothing prohibits running a panel to 100% of its calculated capacity. It is not good practice: it leaves nothing for the next appliance, and heat pumps, induction ranges and EV chargers are exactly the loads people add to older panels. Above about 80% it is worth asking what is coming in the next few years before adding anything.

Technical reviewer
Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region
He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.
The full process is written up in the methodology and editorial policy. Results are engineering guidance, not a code sign-off — see the disclaimer. If a result looks wrong, tell us; corrections are answered before anything else.
Size a house service the way an electrician does: NEC Article 220 standard calculation, with the demand factors that stop a 40 kW house needing a 400 A service.
kVAkVA from the load, full-load current on both windings, and the overcurrent devices — including why the primary is allowed 250% once the secondary is protected.
3ØkW, kVA and kVAr from line voltage and current, with star and delta phase values and what power factor correction would save you.
ΩSolve for voltage, current, resistance or power. Get all four values at once, plus the resistor wattage you actually need.