Service Entrance Conductor Calculator — NEC 310.12 (83% Rule)

Service and feeder conductors for a dwelling, using the 83% allowance — plus the four conditions that decide whether you are allowed to use it at all.

Inputs

Conductor material

Aluminium is standard for service entrance work on cost.

Dwelling unit

310.12 applies to dwellings only.

Carries the entire load of the unit

The condition people miss. A garage or ADU feeder does not qualify.

Results

Service conductors4/0 AWG83% of the device rating, 75 °C column
Ampacity required
166 A
Without the allowance
250 kcmil
Device rating
200 A

Single-family dwelling, entire load, 200 A — 310.12 applies, so the conductors need only 166 A of ampacity.

200 A × 0.83 = 166 A, so 4/0 AWG aluminium in the 75 °C column. Without 310.12 the same service would need 250 kcmil — that is what the rule is worth.

The justification is load diversity: a dwelling never draws its calculated load continuously, and the Article 220 calculation that produced the service size is already conservative. Nothing about the conductor itself changed.

The 75 °C column, not 90 °C — service equipment terminals are listed for 75 °C and 110.14(C) holds you to the lowest-rated part of the circuit. This is the same rule that stops 90 °C insulation buying 90 °C ampacity anywhere else.

Grounding electrode conductor: 4 AWG copper from Table 250.66, sized on the 4/0 AWG service conductors — not on the 200 A device. If the electrode is a ground rod, 250.66(A) caps it at 6 AWG regardless; to a concrete-encased electrode, 250.66(B) caps it at 4 AWG.

The grounded (neutral) conductor is sized separately under 220.61 on the maximum unbalanced load, and it is frequently smaller than the ungrounded conductors — but never smaller than the grounding electrode conductor from Table 250.66.

Diagram

Service conductor with and without the 83% allowance310.12 gives 4/0 AWG; without it the same service needs 250 kcmil.200 A service · 166 A of ampacity neededWith 310.124/0 AWGFull size250 kcmil15% less conductor areaload diversity — a house never draws its calculated load

Worked examples

200 A house service in aluminium

The most common residential service in North America.

4/0 aluminium for 166 A — a size smaller than the rating suggests

The same service in copper

Two sizes smaller in area, several times the price.

2/0 copper

A 200 A feeder to a subpanel

Same size, same house — and the allowance does not apply.

250 kcmil, because it does not carry the entire load

400 A service

The top of the range, and where the rule saves the most.

600 kcmil against 1000 kcmil without the allowance

Reviewed by Salamot Hok, electrician with 10+ years · Last reviewed 17 August 2026

Engineering guidance, not a code sign-off. Verify against the governing standard before relying on this result for safety-critical or code-compliance work.

The one place a conductor may be smaller than its breaker

When to use this: sizing a new service, upgrading an existing one, or checking what an installer has quoted.

Everywhere else in the code a conductor must carry at least what the device ahead of it is rated for. NEC 310.12 is the exception: service and feeder conductors serving the entire load of a dwelling may be sized at 83% of the overcurrent device rating.

A 200 A house service therefore needs conductors rated 166 A, not 200 A — which is 4/0 AWG aluminium rather than 250 kcmil. One full size, on the most expensive conductor in the job.

The justification is load diversity. A house never draws its calculated load continuously, and the Article 220 calculation that produced the service size is already conservative. Nothing about the conductor changed; the code simply stopped double-counting.

Four conditions, all of them

  1. A dwelling unit. Single-family, or an individual unit of a two-family or multifamily dwelling. Never commercial.
  2. The entire load of that unit. This is the one people miss.
  3. Service or feeder conductors. Never branch circuits.
  4. 100 A to 400 A. Outside that range the rule does not exist.

Condition two is where installations go wrong, because the arithmetic looks identical either way. A 200 A feeder to a detached garage, a workshop or an ADU carries part of the load, so it takes full-size conductors from Table 310.16 however large it is. Only the conductors carrying everything qualify.

Table 310.12(A)

The published table, which is simply 83% of each rating resolved against the 75 °C column of Table 310.16 — this calculator derives it rather than transcribing it, which is why a transcription error would show up as a test failure rather than a wrong answer.

Service ratingAmpacity neededCopperAluminiumCopper GEC
100 A83 A4 AWG2 AWG8 AWG
110 A91 A3 AWG1 AWG8 AWG
125 A104 A2 AWG1/0 AWG8 AWG
150 A125 A1 AWG2/0 AWG6 AWG
175 A145 A1/0 AWG3/0 AWG6 AWG
200 A166 A2/0 AWG4/0 AWG4 AWG
225 A187 A3/0 AWG250 kcmil4 AWG
250 A208 A4/0 AWG300 kcmil2 AWG
300 A249 A250 kcmil350 kcmil2 AWG
350 A291 A350 kcmil500 kcmil2 AWG
400 A332 A400 kcmil600 kcmil1/0 AWG

Why the 75 °C column

Service equipment terminals are listed for 75 °C, and 110.14(C) holds the circuit to the lowest-rated component. Using the 90 °C column would give 2/0 AWG → one size smaller for a 200 A service, and it is not permitted. This is the same rule that stops THHN buying 90 °C ampacity anywhere else — our wire size calculator covers it in detail.

The other two conductors

A service has three conductor calculations and they use three different inputs. Getting one right does not get the others right.

ConductorSized fromRule
Ungrounded (hot)83% of the device rating310.12
Grounded (neutral)Maximum unbalanced load220.61
Grounding electrodeSize of the ungrounded conductors250.66

The neutral is usually smaller than the hots, because 220.61 sizes it on the load between neutral and any one ungrounded conductor rather than on the total. Two limits apply: it may not be smaller than the grounding electrode conductor, and a further demand factor applies to the portion above 200 A.

The grounding electrode conductor comes from Table 250.66 and is sized on the service conductors, not on the device. Two caps override the table: 250.66(A) limits the conductor to a ground rod to 6 AWG, and 250.66(B) limits the conductor to a concrete-encased electrode to 4 AWG. A larger conductor into soil achieves nothing — earth is not a fault-current path. Our ground wire size calculator covers the distinction between this and the equipment grounding conductor, which is the most common confusion in Article 250.

Above 400 amps

The allowance stops. Large dwelling services are usually parallel sets under 310.10(G): two or more conductors per phase, each carrying its share. Every set must be identical in length, material, size, insulation and termination method — because current divides by impedance, and a set that is even slightly shorter carries more than its share and overheats while the others loaf.

Two section numbers, one rule

Searching for this turns up both 310.12 and 310.15(B)(7), which causes a lot of confusion. They are the same allowance: it lived at 310.15(B)(7) in older editions and moved to 310.12 in the 2020 code. Older editions also expressed it as a percentage table rather than a flat 83%, so a document citing 310.15(B)(7) may give slightly different sizes. Use the edition your jurisdiction has adopted.

The service size itself comes from an Article 220 load calculation — our load calculator does that arithmetic, and panel capacity tells you whether an existing service has room for what you are adding.

How to use this calculator

  1. Check the four conditions

    A dwelling unit, carrying the entire load of that unit, service or feeder conductors, 100 A to 400 A. All four, or the rule does not apply.

  2. Take 83% of the device rating

    A 200 A service needs conductors rated 166 A, not 200 A.

  3. Read the 75 °C column

    Service equipment terminals are listed for 75 °C, and 110.14(C) holds you to the lowest-rated part of the circuit.

  4. Size the other two conductors separately

    The grounding electrode conductor comes from Table 250.66 on the service conductor size; the neutral comes from 220.61 on the maximum unbalanced load.

Frequently asked questions

What size wire do I need for a 200 amp service?

4/0 aluminium or 2/0 copper for a dwelling, using the 83% allowance in NEC 310.12 — the conductors need only 166 A of ampacity. For a commercial 200 A service the allowance does not apply and you need 250 kcmil aluminium or 3/0 copper.

What is the 83% rule?

NEC 310.12 permits service and feeder conductors serving the entire load of a dwelling unit to be sized at 83% of the overcurrent device rating rather than 100%. The justification is load diversity: a house never draws its calculated load continuously, and the Article 220 calculation that produced the service size is already conservative. Older editions carried the same allowance as 310.15(B)(7), which is why searching turns up two section numbers for one rule.

Does the 83% rule apply to a subpanel feeder?

Only if that feeder carries the entire load of the dwelling unit. A feeder to a detached garage, a workshop or an ADU carries part of the load, so it takes full-size conductors from Table 310.16 however large it is. This is the condition that gets missed most often, because the arithmetic looks identical.

Can I use the 90 °C column for service conductors?

No. Service equipment terminals are listed for 75 °C, and 110.14(C) limits the circuit to the lowest-rated component. The 90 °C column is still the correct starting point for derating calculations, but the final ampacity is capped at 75 °C — the same rule that stops THHN giving 90 °C ampacity anywhere else.

What size grounding electrode conductor do I need?

From Table 250.66, sized on the service conductors rather than on the overcurrent device — a 4/0 aluminium service takes a 4 AWG copper electrode conductor. Two caps override the table: 250.66(A) limits the conductor to a ground rod to 6 AWG, and 250.66(B) limits the conductor to a concrete-encased electrode to 4 AWG. A larger conductor into soil achieves nothing.

Is the neutral the same size as the hots?

Usually not. NEC 220.61 sizes the grounded conductor on the maximum unbalanced load — the load between the neutral and any one ungrounded conductor — which is often considerably less than the total. Two limits apply: it may not be smaller than the grounding electrode conductor from Table 250.66, and a further demand factor applies above 200 A.

What about services above 400 amps?

The allowance stops at 400 A. Above that you size from Table 310.16 in the normal way, and large dwelling services are usually parallel sets under 310.10(G) — each set sized for its share of the load, with every set identical in length, material, size and termination method.

Sources and further reading

How this calculator is checked

Salamot Hok, Technical reviewer

Technical reviewer

Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region

He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.

  • The maths lives in a pure function with its own test suite, asserted against worked examples from published references and standards. A calculator does not ship until those tests pass.
  • 2 sources cited by name and linked, so any figure on the page can be traced back to the document it came from.
  • Last reviewed . Review dates are advanced only when the page is actually re-read, never to look fresh.
  • Unusable input returns no answer. Where the inputs do not describe a real design, the calculator says so and withholds the number rather than printing a plausible-looking wrong one.

Related calculators