200 A house service in aluminium
The most common residential service in North America.
4/0 aluminium for 166 A — a size smaller than the rating suggests
Service and feeder conductors for a dwelling, using the 83% allowance — plus the four conditions that decide whether you are allowed to use it at all.
Aluminium is standard for service entrance work on cost.
310.12 applies to dwellings only.
The condition people miss. A garage or ADU feeder does not qualify.
Single-family dwelling, entire load, 200 A — 310.12 applies, so the conductors need only 166 A of ampacity.
200 A × 0.83 = 166 A, so 4/0 AWG aluminium in the 75 °C column. Without 310.12 the same service would need 250 kcmil — that is what the rule is worth.
The justification is load diversity: a dwelling never draws its calculated load continuously, and the Article 220 calculation that produced the service size is already conservative. Nothing about the conductor itself changed.
The 75 °C column, not 90 °C — service equipment terminals are listed for 75 °C and 110.14(C) holds you to the lowest-rated part of the circuit. This is the same rule that stops 90 °C insulation buying 90 °C ampacity anywhere else.
Grounding electrode conductor: 4 AWG copper from Table 250.66, sized on the 4/0 AWG service conductors — not on the 200 A device. If the electrode is a ground rod, 250.66(A) caps it at 6 AWG regardless; to a concrete-encased electrode, 250.66(B) caps it at 4 AWG.
The grounded (neutral) conductor is sized separately under 220.61 on the maximum unbalanced load, and it is frequently smaller than the ungrounded conductors — but never smaller than the grounding electrode conductor from Table 250.66.
The most common residential service in North America.
4/0 aluminium for 166 A — a size smaller than the rating suggests
Two sizes smaller in area, several times the price.
2/0 copper
Same size, same house — and the allowance does not apply.
250 kcmil, because it does not carry the entire load
The top of the range, and where the rule saves the most.
600 kcmil against 1000 kcmil without the allowance
When to use this: sizing a new service, upgrading an existing one, or checking what an installer has quoted.
Everywhere else in the code a conductor must carry at least what the device ahead of it is rated for. NEC 310.12 is the exception: service and feeder conductors serving the entire load of a dwelling may be sized at 83% of the overcurrent device rating.
A 200 A house service therefore needs conductors rated 166 A, not 200 A — which is 4/0 AWG aluminium rather than 250 kcmil. One full size, on the most expensive conductor in the job.
The justification is load diversity. A house never draws its calculated load continuously, and the Article 220 calculation that produced the service size is already conservative. Nothing about the conductor changed; the code simply stopped double-counting.
Condition two is where installations go wrong, because the arithmetic looks identical either way. A 200 A feeder to a detached garage, a workshop or an ADU carries part of the load, so it takes full-size conductors from Table 310.16 however large it is. Only the conductors carrying everything qualify.
The published table, which is simply 83% of each rating resolved against the 75 °C column of Table 310.16 — this calculator derives it rather than transcribing it, which is why a transcription error would show up as a test failure rather than a wrong answer.
| Service rating | Ampacity needed | Copper | Aluminium | Copper GEC |
|---|---|---|---|---|
| 100 A | 83 A | 4 AWG | 2 AWG | 8 AWG |
| 110 A | 91 A | 3 AWG | 1 AWG | 8 AWG |
| 125 A | 104 A | 2 AWG | 1/0 AWG | 8 AWG |
| 150 A | 125 A | 1 AWG | 2/0 AWG | 6 AWG |
| 175 A | 145 A | 1/0 AWG | 3/0 AWG | 6 AWG |
| 200 A | 166 A | 2/0 AWG | 4/0 AWG | 4 AWG |
| 225 A | 187 A | 3/0 AWG | 250 kcmil | 4 AWG |
| 250 A | 208 A | 4/0 AWG | 300 kcmil | 2 AWG |
| 300 A | 249 A | 250 kcmil | 350 kcmil | 2 AWG |
| 350 A | 291 A | 350 kcmil | 500 kcmil | 2 AWG |
| 400 A | 332 A | 400 kcmil | 600 kcmil | 1/0 AWG |
Service equipment terminals are listed for 75 °C, and 110.14(C) holds the circuit to the lowest-rated component. Using the 90 °C column would give 2/0 AWG → one size smaller for a 200 A service, and it is not permitted. This is the same rule that stops THHN buying 90 °C ampacity anywhere else — our wire size calculator covers it in detail.
A service has three conductor calculations and they use three different inputs. Getting one right does not get the others right.
| Conductor | Sized from | Rule |
|---|---|---|
| Ungrounded (hot) | 83% of the device rating | 310.12 |
| Grounded (neutral) | Maximum unbalanced load | 220.61 |
| Grounding electrode | Size of the ungrounded conductors | 250.66 |
The neutral is usually smaller than the hots, because 220.61 sizes it on the load between neutral and any one ungrounded conductor rather than on the total. Two limits apply: it may not be smaller than the grounding electrode conductor, and a further demand factor applies to the portion above 200 A.
The grounding electrode conductor comes from Table 250.66 and is sized on the service conductors, not on the device. Two caps override the table: 250.66(A) limits the conductor to a ground rod to 6 AWG, and 250.66(B) limits the conductor to a concrete-encased electrode to 4 AWG. A larger conductor into soil achieves nothing — earth is not a fault-current path. Our ground wire size calculator covers the distinction between this and the equipment grounding conductor, which is the most common confusion in Article 250.
The allowance stops. Large dwelling services are usually parallel sets under 310.10(G): two or more conductors per phase, each carrying its share. Every set must be identical in length, material, size, insulation and termination method — because current divides by impedance, and a set that is even slightly shorter carries more than its share and overheats while the others loaf.
Searching for this turns up both 310.12 and 310.15(B)(7), which causes a lot of confusion. They are the same allowance: it lived at 310.15(B)(7) in older editions and moved to 310.12 in the 2020 code. Older editions also expressed it as a percentage table rather than a flat 83%, so a document citing 310.15(B)(7) may give slightly different sizes. Use the edition your jurisdiction has adopted.
The service size itself comes from an Article 220 load calculation — our load calculator does that arithmetic, and panel capacity tells you whether an existing service has room for what you are adding.
A dwelling unit, carrying the entire load of that unit, service or feeder conductors, 100 A to 400 A. All four, or the rule does not apply.
A 200 A service needs conductors rated 166 A, not 200 A.
Service equipment terminals are listed for 75 °C, and 110.14(C) holds you to the lowest-rated part of the circuit.
The grounding electrode conductor comes from Table 250.66 on the service conductor size; the neutral comes from 220.61 on the maximum unbalanced load.
4/0 aluminium or 2/0 copper for a dwelling, using the 83% allowance in NEC 310.12 — the conductors need only 166 A of ampacity. For a commercial 200 A service the allowance does not apply and you need 250 kcmil aluminium or 3/0 copper.
NEC 310.12 permits service and feeder conductors serving the entire load of a dwelling unit to be sized at 83% of the overcurrent device rating rather than 100%. The justification is load diversity: a house never draws its calculated load continuously, and the Article 220 calculation that produced the service size is already conservative. Older editions carried the same allowance as 310.15(B)(7), which is why searching turns up two section numbers for one rule.
Only if that feeder carries the entire load of the dwelling unit. A feeder to a detached garage, a workshop or an ADU carries part of the load, so it takes full-size conductors from Table 310.16 however large it is. This is the condition that gets missed most often, because the arithmetic looks identical.
No. Service equipment terminals are listed for 75 °C, and 110.14(C) limits the circuit to the lowest-rated component. The 90 °C column is still the correct starting point for derating calculations, but the final ampacity is capped at 75 °C — the same rule that stops THHN giving 90 °C ampacity anywhere else.
From Table 250.66, sized on the service conductors rather than on the overcurrent device — a 4/0 aluminium service takes a 4 AWG copper electrode conductor. Two caps override the table: 250.66(A) limits the conductor to a ground rod to 6 AWG, and 250.66(B) limits the conductor to a concrete-encased electrode to 4 AWG. A larger conductor into soil achieves nothing.
Usually not. NEC 220.61 sizes the grounded conductor on the maximum unbalanced load — the load between the neutral and any one ungrounded conductor — which is often considerably less than the total. Two limits apply: it may not be smaller than the grounding electrode conductor from Table 250.66, and a further demand factor applies above 200 A.
The allowance stops at 400 A. Above that you size from Table 310.16 in the normal way, and large dwelling services are usually parallel sets under 310.10(G) — each set sized for its share of the load, with every set identical in length, material, size and termination method.

Technical reviewer
Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region
He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.
The full process is written up in the methodology and editorial policy. Results are engineering guidance, not a code sign-off — see the disclaimer. If a result looks wrong, tell us; corrections are answered before anything else.
Size a house service the way an electrician does: NEC Article 220 standard calculation, with the demand factors that stop a 40 kW house needing a 400 A service.
⚡Whether your existing panel has room for a new circuit — in amps and in breaker spaces, which are different constraints and only one of them is visible through the door.
AWGWhat size wire you need, from the load, the run length and the conditions — sized against both NEC ampacity and voltage drop, with the terminal temperature rule that stops 90 °C wire giving 90 °C ampacity.
EGCEquipment grounding conductor size from the breaker rating — including the 250.122(B) proportional increase almost every other calculator leaves out when a run is upsized for voltage drop.