45 kVA, 480 → 208 V
The standard commercial step-down. Two windings, two very different currents.
54.1 A primary, 124.9 A secondary
kVA from the load, full-load current on both windings, and the overcurrent devices — including why the primary is allowed 250% once the secondary is protected.
kVA on the secondary.
Headroom added before rounding to a standard size.
Changes the primary ceiling from 125% to 250%.
40.0 kVA of load plus 25% spare is 50.0 kVA, so the next standard size is 75 kVA. Standard sizes are widely spaced above 100 kVA, so the spare you actually get is often much more than you asked for.
Two windings, two currents: 90.2 A on the 480 V primary and 208.2 A on the 208 V secondary — a ratio of 2.31. Size each set of conductors from its own winding. Using the secondary current for the primary conductors is a common and expensive mistake.
Secondary protected at 125%, so the primary device only has to survive a fault and may go to 250% — which is what lets magnetising inrush through without nuisance tripping.
Primary device: 250% of 90.2 A = 225.5 A → 225 A. The higher percentages are hard ceilings, so this rounds DOWN — you may not exceed them.
Secondary device: 125% of 208.2 A = 260.2 A → 300 A. This is what actually protects the transformer from overload, which is why the primary is allowed to be so much larger.
Secondary conductors are one of the few places the code lets a conductor run unprotected at its origin — 240.21(C). The 10 ft tap rule needs conductors rated at least 10% of the device ahead of them, terminating in a single overcurrent device, in a raceway. The 25 ft rule is one third, with the turns ratio applied.
The standard commercial step-down. Two windings, two very different currents.
54.1 A primary, 124.9 A secondary
Same transformer, no secondary device. Watch the ceiling drop to 125%.
70 A primary device — and likely to trip on energisation
Transformers are rated in kVA. Power factor decides how much you need.
40 kW at 0.8 pf is 50 kVA; plus 25% spare gives 75 kVA
Under 9 A on the primary, so the percentages step up sharply.
167% permitted rather than 125%
When to use this: specifying a dry-type transformer, checking an existing one has capacity, or sizing the conductors and devices either side of it.
A transformer has a different full-load current on each winding, and they are not interchangeable. A 45 kVA 480→208 V unit draws 54.1 A on the primary and delivers 124.9 A on the secondary — a ratio of 2.31, which is exactly the inverse of the voltage ratio.
Size the primary conductors from the primary current and the secondary conductors from the secondary current. Using one for the other gives conductors less than half the size they need to be, and it is a mistake that survives inspection because nothing looks wrong until the transformer is loaded.
I = kVA × 1000 / (√3 × V). The √3 is geometry, not power factor — kVA is apparent power, so power factor does not enter this at all.
| kVA | 208 V | 240 V | 480 V | 600 V |
|---|---|---|---|---|
| 15 | 41.6 A | 36.1 A | 18.0 A | 14.4 A |
| 30 | 83.3 A | 72.2 A | 36.1 A | 28.9 A |
| 45 | 124.9 A | 108.3 A | 54.1 A | 43.3 A |
| 75 | 208.2 A | 180.4 A | 90.2 A | 72.2 A |
| 112.5 | 312.3 A | 270.6 A | 135.3 A | 108.3 A |
| 150 | 416.4 A | 360.8 A | 180.4 A | 144.3 A |
| 225 | 624.5 A | 541.3 A | 270.6 A | 216.5 A |
| 300 | 832.7 A | 721.7 A | 360.8 A | 288.7 A |
| 500 | 1387.9 A | 1202.8 A | 601.4 A | 481.1 A |
| 750 | 2081.8 A | 1804.2 A | 902.1 A | 721.7 A |
Transformers are rated in kVA rather than kW because the winding heats on current, and current follows apparent power. Your load is probably quoted in kW, so divide by the power factor first: 40 kW at 0.8 is 50 kVA of transformer, and the same 40 kW at unity is 40 kVA.
Then add spare capacity — 20 to 25% is usual — and round up. Note how widely spaced the standard sizes are above 100 kVA: 45, 75, 112.5, 150, 225, 300. A 50 kVA requirement takes a 75 kVA transformer, so the spare you actually get is often far more than you asked for.
This is the part that decides whether the installation stays energised, and it turns on a single question: is the secondary separately protected?
| Arrangement | Primary ceiling | Secondary ceiling | Device on our 45 kVA |
|---|---|---|---|
| Primary only, 9 A or more | 125% | — | 70 A |
| Primary only, under 9 A | 167% | — | — |
| Primary only, under 2 A | 300% | — | — |
| Secondary protected | 250% | 125% | 125 A |
The reason for 250% is magnetising inrush. Energising a transformer draws 8 to 12 times full-load current for a few cycles while the core flux settles. It does the transformer no harm and it is entirely capable of tripping a device sitting at 125% of full load.
With a secondary device in place the primary no longer has to protect against overload — the secondary does that — so it is free to be large enough to ride through inrush. With primary protection only, you are held to 125% and nuisance tripping on switch-on becomes your problem. It is the most common reason a correctly sized installation will not stay on.
Secondary protected at 125%, so the primary device only has to survive a fault and may go to 250% — which is what lets magnetising inrush through without nuisance tripping.
450.3(B) note 1 permits the next standard size up where 125% does not land on one — 54.1 A × 1.25 = 67.7 A, so 70 A. The higher percentages are hard ceilings that may not be exceeded, so they round down: 54.1 A × 2.5 = 135.3 A takes a 125 A device, not the next size above.
Transformer secondary conductors are one of the few places the code lets a conductor run without overcurrent protection at its origin — 240.21(C), and the allowance depends on length.
Neither is a general permission to leave conductors unprotected, and the conditions are where installations fail inspection — particularly the requirement to land in a single device rather than a small distribution board.
Once you have the two currents, our wire size calculator handles the conductors either side, and panel capacity checks whether the secondary distribution has room.
From the connected load. If you have kW, divide by the power factor — transformers are rated in apparent power because the winding heats on current.
Then round up to a standard size. Above 100 kVA the standard sizes are widely spaced, so you often get considerably more spare than you asked for.
Each winding has its own. Size the primary conductors from the primary current and the secondary conductors from the secondary current.
With a secondary device at 125%, the primary may go to 250%. Without one the primary is capped at 125%, which is close enough to full load that inrush will often trip it.
Total the connected load in kVA, add spare capacity — 20–25% is usual — and round up to a standard size. A 40 kVA load with 25% spare is 50 kVA, which takes a 75 kVA transformer because the standard sizes jump from 45 to 75. If your load is in kW, divide by the power factor first.
For three phase, kVA × 1000 ÷ (1.732 × voltage). For single phase, kVA × 1000 ÷ voltage. Do it once for each winding: a 45 kVA 480→208 V transformer draws 54.1 A on the primary and delivers 124.9 A on the secondary. The 1.732 is √3 and comes from the geometry of three-phase power, not from any power factor.
It affects how much kVA you need, not the current a given kVA draws. A 40 kW load at 0.8 power factor is 50 kVA of transformer; the same 40 kW at unity is 40 kVA. Once the transformer is rated, its full-load current follows from the kVA and the voltage alone — which is exactly why transformers are rated in kVA rather than kW.
Because with a secondary device in place, the primary device no longer has to protect against overload — the secondary handles that. It only has to clear a fault. That freedom is needed: energising a transformer draws 8 to 12 times full-load current for a few cycles, and a device sitting at 125% will often trip on switch-on. With primary protection only, 450.3(B) holds you to 125% and nuisance tripping becomes your problem.
No, and it is an expensive mistake. The currents differ by the turns ratio — on a 480→208 V transformer the secondary current is 2.3 times the primary. Sizing 208 V conductors from a 54 A primary figure gives conductors less than half the size they need to be.
NEC 240.21(C). Secondary conductors are one of the few places the code permits a conductor to run without overcurrent protection at its origin, subject to length. The 10 ft rule needs conductors rated at least 10% of the device ahead of them, terminating in a single overcurrent device, enclosed in a raceway. The 25 ft rule requires one third of the primary device rating multiplied by the turns ratio. Neither is a general permission to leave conductors unprotected.
Because a device at 125% of a 1.5 A primary would be a 2 A device, which is not a standard product, and because inrush is proportionally just as large on a small transformer as a large one. 450.3(B) therefore allows 167% below 9 A and 300% below 2 A with primary protection only.
The magnetising current drawn when a transformer is first energised, before the core flux settles — typically 8 to 12 times full-load current, decaying over a few cycles. It does no harm to the transformer and it is entirely capable of tripping an instantaneous device sized close to full load. It is the single most common reason a correctly sized installation will not stay energised.

Technical reviewer
Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region
He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.
The full process is written up in the methodology and editorial policy. Results are engineering guidance, not a code sign-off — see the disclaimer. If a result looks wrong, tell us; corrections are answered before anything else.
kW, kVA and kVAr from line voltage and current, with star and delta phase values and what power factor correction would save you.
kVASize a house service the way an electrician does: NEC Article 220 standard calculation, with the demand factors that stop a 40 kW house needing a 400 A service.
AWGWhat size wire you need, from the load, the run length and the conditions — sized against both NEC ampacity and voltage drop, with the terminal temperature rule that stops 90 °C wire giving 90 °C ampacity.
FLAFull load current from motor kW or hp, including efficiency — the term most calculators drop, which understates the current by 10–15%.