Transformer Sizing Calculator — kVA, FLA and NEC 450.3

kVA from the load, full-load current on both windings, and the overcurrent devices — including why the primary is allowed 250% once the secondary is protected.

Inputs

Phase
V

V

Load given as

kVA on the secondary.

%

Headroom added before rounding to a standard size.

Secondary separately protected

Changes the primary ceiling from 125% to 250%.

Results

Transformer75next standard kVA
kVA required
50
Primary full-load current
90.21 A
Secondary full-load current
208.2 A
Primary device
225 A
Secondary device
300 A
Primary ceiling
250 %

40.0 kVA of load plus 25% spare is 50.0 kVA, so the next standard size is 75 kVA. Standard sizes are widely spaced above 100 kVA, so the spare you actually get is often much more than you asked for.

Two windings, two currents: 90.2 A on the 480 V primary and 208.2 A on the 208 V secondary — a ratio of 2.31. Size each set of conductors from its own winding. Using the secondary current for the primary conductors is a common and expensive mistake.

Secondary protected at 125%, so the primary device only has to survive a fault and may go to 250% — which is what lets magnetising inrush through without nuisance tripping.

Primary device: 250% of 90.2 A = 225.5 A → 225 A. The higher percentages are hard ceilings, so this rounds DOWN — you may not exceed them.

Secondary device: 125% of 208.2 A = 260.2 A → 300 A. This is what actually protects the transformer from overload, which is why the primary is allowed to be so much larger.

Secondary conductors are one of the few places the code lets a conductor run unprotected at its origin — 240.21(C). The 10 ft tap rule needs conductors rated at least 10% of the device ahead of them, terminating in a single overcurrent device, in a raceway. The 25 ft rule is one third, with the turns ratio applied.

Diagram

Transformer windings and currents75 kVA: 90.2 A at 480 V on the primary, 208.2 A at 208 V on the secondary.75 kVA — one current per windingPRIMARY90.2 A480 VSECONDARY208.2 A208 Vdevice 225 Adevice 300 Aratio 2.31× — size each side on its own current

Worked examples

45 kVA, 480 → 208 V

The standard commercial step-down. Two windings, two very different currents.

54.1 A primary, 124.9 A secondary

Primary protection only

Same transformer, no secondary device. Watch the ceiling drop to 125%.

70 A primary device — and likely to trip on energisation

Sized from a kW load

Transformers are rated in kVA. Power factor decides how much you need.

40 kW at 0.8 pf is 50 kVA; plus 25% spare gives 75 kVA

Small control transformer

Under 9 A on the primary, so the percentages step up sharply.

167% permitted rather than 125%

Reviewed by Salamot Hok, electrician with 10+ years · Last reviewed 17 August 2026

Engineering guidance, not a code sign-off. Verify against the governing standard before relying on this result for safety-critical or code-compliance work.

Two windings, two currents

When to use this: specifying a dry-type transformer, checking an existing one has capacity, or sizing the conductors and devices either side of it.

A transformer has a different full-load current on each winding, and they are not interchangeable. A 45 kVA 480→208 V unit draws 54.1 A on the primary and delivers 124.9 A on the secondary — a ratio of 2.31, which is exactly the inverse of the voltage ratio.

Size the primary conductors from the primary current and the secondary conductors from the secondary current. Using one for the other gives conductors less than half the size they need to be, and it is a mistake that survives inspection because nothing looks wrong until the transformer is loaded.

Full-load current, three phase

I = kVA × 1000 / (√3 × V). The √3 is geometry, not power factor — kVA is apparent power, so power factor does not enter this at all.

kVA208 V240 V480 V600 V
1541.6 A36.1 A18.0 A14.4 A
3083.3 A72.2 A36.1 A28.9 A
45124.9 A108.3 A54.1 A43.3 A
75208.2 A180.4 A90.2 A72.2 A
112.5312.3 A270.6 A135.3 A108.3 A
150416.4 A360.8 A180.4 A144.3 A
225624.5 A541.3 A270.6 A216.5 A
300832.7 A721.7 A360.8 A288.7 A
5001387.9 A1202.8 A601.4 A481.1 A
7502081.8 A1804.2 A902.1 A721.7 A

Where the kVA comes from

Transformers are rated in kVA rather than kW because the winding heats on current, and current follows apparent power. Your load is probably quoted in kW, so divide by the power factor first: 40 kW at 0.8 is 50 kVA of transformer, and the same 40 kW at unity is 40 kVA.

Then add spare capacity — 20 to 25% is usual — and round up. Note how widely spaced the standard sizes are above 100 kVA: 45, 75, 112.5, 150, 225, 300. A 50 kVA requirement takes a 75 kVA transformer, so the spare you actually get is often far more than you asked for.

Protection: the 125% / 250% distinction

This is the part that decides whether the installation stays energised, and it turns on a single question: is the secondary separately protected?

ArrangementPrimary ceilingSecondary ceilingDevice on our 45 kVA
Primary only, 9 A or more125%70 A
Primary only, under 9 A167%
Primary only, under 2 A300%
Secondary protected250%125%125 A

The reason for 250% is magnetising inrush. Energising a transformer draws 8 to 12 times full-load current for a few cycles while the core flux settles. It does the transformer no harm and it is entirely capable of tripping a device sitting at 125% of full load.

With a secondary device in place the primary no longer has to protect against overload — the secondary does that — so it is free to be large enough to ride through inrush. With primary protection only, you are held to 125% and nuisance tripping on switch-on becomes your problem. It is the most common reason a correctly sized installation will not stay on.

Secondary protected at 125%, so the primary device only has to survive a fault and may go to 250% — which is what lets magnetising inrush through without nuisance tripping.

Rounding goes different ways

450.3(B) note 1 permits the next standard size up where 125% does not land on one — 54.1 A × 1.25 = 67.7 A, so 70 A. The higher percentages are hard ceilings that may not be exceeded, so they round down: 54.1 A × 2.5 = 135.3 A takes a 125 A device, not the next size above.

Secondary conductors

Transformer secondary conductors are one of the few places the code lets a conductor run without overcurrent protection at its origin — 240.21(C), and the allowance depends on length.

  • 10 ft tap. Conductor ampacity at least 10% of the device protecting them, terminating in a single overcurrent device, enclosed in a raceway.
  • 25 ft tap. Ampacity at least one third of the primary device rating multiplied by the turns ratio, terminating in a single device, protected from physical damage.

Neither is a general permission to leave conductors unprotected, and the conditions are where installations fail inspection — particularly the requirement to land in a single device rather than a small distribution board.

Details worth knowing

  • Impedance sets fault current. A transformer marked 5% Z will deliver roughly 20 times its full-load current into a bolted secondary fault. That figure decides the interrupting rating of everything downstream, and it is on the nameplate.
  • A separately derived system needs its own grounding. 250.30 requires a system bonding jumper and a grounding electrode conductor at the transformer. The neutral and ground are bonded there and nowhere downstream.
  • Delta-wye shifts the phase by 30°. It matters when paralleling transformers or connecting to an existing system, and it is invisible until it goes wrong.
  • Nonlinear loads may need a K-rated unit. Harmonic currents heat the windings well beyond what the kVA rating suggests. A standard transformer feeding heavy electronics is a common cause of unexplained overheating.

Once you have the two currents, our wire size calculator handles the conductors either side, and panel capacity checks whether the secondary distribution has room.

How to use this calculator

  1. Work out the kVA

    From the connected load. If you have kW, divide by the power factor — transformers are rated in apparent power because the winding heats on current.

  2. Add spare capacity

    Then round up to a standard size. Above 100 kVA the standard sizes are widely spaced, so you often get considerably more spare than you asked for.

  3. Read both full-load currents

    Each winding has its own. Size the primary conductors from the primary current and the secondary conductors from the secondary current.

  4. Decide on secondary protection

    With a secondary device at 125%, the primary may go to 250%. Without one the primary is capped at 125%, which is close enough to full load that inrush will often trip it.

Frequently asked questions

What size transformer do I need?

Total the connected load in kVA, add spare capacity — 20–25% is usual — and round up to a standard size. A 40 kVA load with 25% spare is 50 kVA, which takes a 75 kVA transformer because the standard sizes jump from 45 to 75. If your load is in kW, divide by the power factor first.

How do I calculate transformer full-load current?

For three phase, kVA × 1000 ÷ (1.732 × voltage). For single phase, kVA × 1000 ÷ voltage. Do it once for each winding: a 45 kVA 480→208 V transformer draws 54.1 A on the primary and delivers 124.9 A on the secondary. The 1.732 is √3 and comes from the geometry of three-phase power, not from any power factor.

Does power factor affect transformer sizing?

It affects how much kVA you need, not the current a given kVA draws. A 40 kW load at 0.8 power factor is 50 kVA of transformer; the same 40 kW at unity is 40 kVA. Once the transformer is rated, its full-load current follows from the kVA and the voltage alone — which is exactly why transformers are rated in kVA rather than kW.

Why is the primary breaker allowed to be 250% of full load?

Because with a secondary device in place, the primary device no longer has to protect against overload — the secondary handles that. It only has to clear a fault. That freedom is needed: energising a transformer draws 8 to 12 times full-load current for a few cycles, and a device sitting at 125% will often trip on switch-on. With primary protection only, 450.3(B) holds you to 125% and nuisance tripping becomes your problem.

Can I use the primary current for the secondary conductors?

No, and it is an expensive mistake. The currents differ by the turns ratio — on a 480→208 V transformer the secondary current is 2.3 times the primary. Sizing 208 V conductors from a 54 A primary figure gives conductors less than half the size they need to be.

What are the rules for transformer secondary conductors?

NEC 240.21(C). Secondary conductors are one of the few places the code permits a conductor to run without overcurrent protection at its origin, subject to length. The 10 ft rule needs conductors rated at least 10% of the device ahead of them, terminating in a single overcurrent device, enclosed in a raceway. The 25 ft rule requires one third of the primary device rating multiplied by the turns ratio. Neither is a general permission to leave conductors unprotected.

Why do small transformers get higher percentages?

Because a device at 125% of a 1.5 A primary would be a 2 A device, which is not a standard product, and because inrush is proportionally just as large on a small transformer as a large one. 450.3(B) therefore allows 167% below 9 A and 300% below 2 A with primary protection only.

What is transformer inrush and why does it matter?

The magnetising current drawn when a transformer is first energised, before the core flux settles — typically 8 to 12 times full-load current, decaying over a few cycles. It does no harm to the transformer and it is entirely capable of tripping an instantaneous device sized close to full load. It is the single most common reason a correctly sized installation will not stay energised.

Sources and further reading

How this calculator is checked

Salamot Hok, Technical reviewer

Technical reviewer

Electrician · 10+ years of installation work in Bangladesh and the wider South Asian region

He reads the result the way an installer would: are the defaults values people actually meet, does the warning fire where you would stop and think, and is the answer something you could buy and fit? The code figures themselves come from the published standards cited below, not from him — that boundary is set out on his profile.

  • The maths lives in a pure function with its own test suite, asserted against worked examples from published references and standards. A calculator does not ship until those tests pass.
  • 2 sources cited by name and linked, so any figure on the page can be traced back to the document it came from.
  • Last reviewed . Review dates are advanced only when the page is actually re-read, never to look fresh.
  • Unusable input returns no answer. Where the inputs do not describe a real design, the calculator says so and withholds the number rather than printing a plausible-looking wrong one.

Related calculators